Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert® IntelliSlot® Modbus/BACnet IP 146
Output
Source 40050 1 —
1 = Other
2 = None
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
Frequency 40051 1 10 Units: Hz
Number Lines 40052 1
Voltage L1 40053 1 Units: V
Voltage L2 40054 1 Units: V
Voltage L3 40055 1 Units: V
Current L1 40056 1 10 Units: A
Current L2 40057 1 10 Units: A
Current L3 40058 1 10 Units: A
Real Power L1 40059 1 10 Units: kW
Real Power L2 40060 1 10 Units: kW
Real Power L3 40061 1 10 Units: kW
Percent Load L1 40062 1 Units: %
Percent Load L2 40063 1 Units: %
Percent Load L3 40064 1 Units: %
Bypass
Line Bads 40070 1
Frequency 40071 1 10 Units: Hz
Number Lines 40072 1
Voltage L1 40073 1 Units: V
Voltage L2 40074 1 Units: V
Voltage L3 40075 1 Units: V
Current L1 40076 1 10 Units: A
Current L2 40077 1 10 Units: A
Current L3 40078 1 10 Units: A
Alarms
Alarms Present 40087 1 Bit 0
On Battery 40087 1 Bit 2
Low Battery 40087 1 Bit 3
Depleted Battery 40087 1 Bit 4
Temperature Bad 40087 1 Bit 5
Input Bad 40087 1 Bit 6
Output Overload 40088 1 Bit 0
On Bypass 40088 1 Bit 1
Bypass Bad 40088 1 Bit 2
Charger Failed 40088 1 Bit 5
Fan Failure 40089 1 Bit 0
General Fault 40089 1 Bit 2
Table 54 Liebert NX 225-600kVA UPS - Input and Holding3 (continued)
Data Description Input
Holding
Register
# of
Reg Scale Notes/Units