BACnet Communications - UPS Systems
309 Liebert® IntelliSlot® Modbus/BACnet IP
System Output Apparent Power L2 Analog_Value 71 5869_1 RD Units: kVA
System Output Power Analog_Value 72 4208_1 RD Units: kW
System Output Power L1 Analog_Value 73 5859_1 RD Units: kW
System Output Power L2 Analog_Value 74 5860_1 RD Units: kW
System Output Pct Power L1 Analog_Value 75 4223_1 RD Units: %
System Output Pct Power L2 Analog_Value 76 4224_1 RD Units: %
Maximum Load Alarm Limit Analog_Value 77 5813_1 RW Units: kVA
Shutdown After Delay Analog_Value 78 5814_1 RW Units: sec
Reboot After Delay Analog_Value 79 5815_1 RW Units: sec
Output On Delay Analog_Value 80 5816_1 RW Units: sec
System Status
System Capacity Analog_Value 91 5821_1 RD Units: kVA
Frame Capacity Analog_Value 92 5822_1 RD Units: kVA
Number of Installed Power Modules Analog_Value 93 5823_1 RD
Number Of Active Power Modules Analog_Value 94 5824_1 RD
Number Of Power Modules With Warnings Analog_Value 95 5825_1 RD
Number Of Failed Power Modules Analog_Value 96 5826_1 RD
Number of Installed Battery Strings Analog_Value 97 5827_1 RD
Number of Active Battery Strings Analog_Value 98 5828_1 RD
Number of Battery Strings With Warnings Analog_Value 99 5829_1 RD
Number of Failed Battery Strings Analog_Value 100 5830_1 RD
Auto Restart Delay Analog_Value 101 5852_1 RW Units: sec
No Load Warning Current Threshold Analog_Value 102 5866_1 RW Units: A AC
No Load Warning Delay Analog_Value 103 5867_1 RW Units: min
BatteryModule 1
Battery String Voltage Analog_Value 114 5843_1 RD Units: VDC
Battery Module Temperature Analog_Value 115 5844_1 RD Units: deg C
Battery Module Temperature Analog_Value 10115 5844_1_deg_F RD Units: deg F
Number of Discharge Cycles Analog_Value 116 5845_1 RD
Accumulated Discharge Time Analog_Value 117 5846 _1 RD Units: hr
BatteryModule 2
Battery String Voltage Analog_Value 128 5843_2 RD Units: VDC
Battery Module Temperature Analog_Value 129 5844_2 RD Units: deg C
Battery Module Temperature Analog_Value 10129 5844_2_deg_F RD Units: deg F
Number of Discharge Cycles Analog_Value 130 5845_2 RD
Accumulated Discharge Time Analog_Value 131 5846 _2 RD Units: hr
BatteryModule 80
Battery String Voltage Analog_Value 1220 5843_80 RD Units: VDC
Battery Module Temperature Analog_Value 1221 5844_80 RD Units: deg C
Battery Module Temperature Analog_Value 11221 5844_80_deg_F RD Units: deg F
Number of Discharge Cycles Analog_Value 1222 5845_80 RD
Accumulated Discharge Time Analog_Value 1223 5846_80 RD Units: hr
System Configuration
System Date and Time Analog_Value 1234 4293_1 RW
Table 103 Liebert APS - Analog Data (continued)
Data Label Object Type Instance Object Name Access Notes