Modbus 485 and Modbus IP Protocols - UPS Systems
141 Liebert® IntelliSlot® Modbus/BACnet IPTable 52 Liebert NX - Status and Coil
Data Description Status Coil
Number
of Bits Scale Notes / Units
Economode 10005 5
DC-To-DC Converter On 10042
Battery Charge Compensation 10046
Inverter Ready 10047
Power Factor Correction State 10050
Battery Charge Mode 10051
Load On Inverter 10073
Bypass Active 10074
Battery Under Test 10082
Load On Battery 10128
Overload Transfer To Bypass 10131
Input Switch Open 10137
Generator Disconnected 10141
Bypass Transfer Count Block 10147
Static Bypass Switch Disabled 10148
Low Battery - Shutdown Imminent 10152
Output Overload 10154
UPS Load Joint Mode 10156
Output Off 10158
Inverter Unsynchronized 10160
Main Neutral Lost 10161
Fan Failure 10169
Ambient Over Temperature 10173
Rectifier Over Temperature 10174
Rectifier Inductor Over Temperature 10175
Inverter Over Temperature 10176
Inverter Inductor Over Temperature 10177
Battery Converter Over Temperature 10179
DC Bus Balancer Over Temperature 10180
Input Power Supply Fail 10186
Input BrownOut 10189
Bad Input Frequency 10190
Bypass Phase Rotation Error 10191
Bypass Phase Loss 10201
Bypass Input Voltage/Frequency Fault 10202
Output Fuse Blown 10217
Output Over Voltage 10219
Charger Failed 10234
Battery Fault 10235
Battery Contact Fail 10236
Battery Converter Over Current 10237
Battery Converter Fail 10238
DC Bus Balancer Over Current 10239