Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert® IntelliSlot® Modbus/BACnet IP 128
System Output Apparent Power L1 30473 1 100 Units : kVA
Uint 16
System Output Apparent Power L2 30474 1 100 Units : kVA
Uint 16
System Output Power 30475 1 100 Units : kW
Uint 16
System Output Power L1 30476 1 100 Units : kW
Uint 16
System Output Power L2 30477 1 100 Units : kW
Uint 16
System Output Pct Power L1 30478 1 10 Units : %
Uint 16
System Output Pct Power L2 30479 1 10 Units : %
Uint 16
Output Qualification Status 30480 1
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
Maximum Load Alarm Limit 30481 40481 1 10 Units : kVA
Uint16
Shutdown After Delay 30482 40482 1 Units : sec
Uint 16
Reboot After Delay 30483 40483 1 Units : sec
Uint 16
Output On Delay 30484 40484 1 Units : sec
Uint 16
Inverter
Inverter On/Off State 30495 1 0 = off
1 = on
System Set To Operate With 30496 40496 1 0 = No Redundancy
1 = Redundancy
System Capacity 30507 1 1000 Units : kVA
Uint 16
Frame Capacity 30508 1 1000 Units : kVA
Uint 16
Number of Installed Power Modules 30509 1 Uint 16
Number Of Active Power Modules 30510 1 Uint 16
Number Of Power Modules With Warnings 30511 1 Uint 16
Number Of Failed Power Modules 30512 1 Uint 16
Number of Installed Battery Strings 30513 1 Uint 16
Number of Active Battery Strings 30514 1 Uint 16
Number of Battery Strings With Warnings 30515 1 Uint 16
Number of Failed Battery Strings 30516 1 Uint 16
UPS Output Source 30517 1
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
System Status 30518 1
1 = Normal Operation
2 = StartUp
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
Table 44 Liebert APS - Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units