BACnet Communications - UPS Systems
327 Liebert® IntelliSlot® Modbus/BACnet IPTable 108 Liebert NXL - 60Hz, UL version (Model 40) - Multistate Data
Data Label
Object
Type Instance
Object
Name Access Notes
Liebert
NXL Type
Input
Input Qualification Status MultiState_Value 1 4735_1 RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
SMS, 1+N,
N+1
Bypass
Static Bypass Switch MultiState_Value 12 4736_1 RD 1 = off SMS, 1+N,
SCC
Bypass Qualification Status MultiState_Value 13 4737_1 RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
SMS, 1+N,
SCC
Battery
UPS Battery Status MultiState_Value 24 4871_1 RD
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
SMS, 1+N,
N+1
DC Bus
DC Bus Qualification Status MultiState_Value 35 4743_1 RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
SMS, 1+N,
N+1
Output
Output Qualification Status MultiState_Value 46 4744_1 RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
SMS, 1+N,
N+1, SCC
Inverter
Inverter Output Qualification
Status MultiState_Value 57 4745_1 RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
SMS, 1+N,
N+1
Inverter On/Off State MultiState_Value 58 4746_1 RD 1 = off
2 = on
SMS, 1+N,
N+1
Rectifier
Rectifier Pulse Count MultiState_Value 69 4257_1 RD
1 = 6 Pulse
2 = 12 Pulse
3 = 18 Pulse
4 = 24 Pulse
SMS, 1+N,
N+1
Rectifier Input Passive Filter MultiState_Value 70 4258_1 RD 1 = Not Installed
2 = Installed
SMS, 1+N,
N+1
Rectifier Passive Filter
Switch MultiState_Value 71 4301_1 RD 1 = Not Installed
2 = Installed
SMS, 1+N,
N+1
Rectifier Active Filter MultiState_Value 72 4302_1 RD 1 = Not Installed
2 = Installed
SMS, 1+N,
N+1
Rectifier Status MultiState_Value 73 4748_1 RD 1 = off
2 = on
SMS, 1+N,
N+1