BACnet Communications - Thermal Management Products
283 Liebert® IntelliSlot® Modbus/BACnet IPTable 94 Liebert XDP, Liebert XDC - Multistate Data
Controller Liebert iCOM® v4
Data Label Object Type Instance
Object
Name Access Notes
External Air
Ext Air Sensor A Over Temp - Event Control Multistate_Value 1 4602_1 RW 1 = Disabled
2 = Enabled
Ext Air Sensor A Over Temp - Event Type Multistate_Value 2 4603_1 RW
1 = Message
2 = Warning
3 = Alarm
Ext Air Sensor B Over Temp - Event Control Multistate_Value 3 4605_1 RW 1 = Disabled
2 = Enabled
Ext Air Sensor B Over Temp - Event Type Multistate_Value 4 4606_1 RW
1 = Message
2 = Warning
3 = Alarm
Ext Air Sensor A Under Temp - Event Control Multistate_Value 5 4609_1 RW 1 = Disabled
2 = Enabled
Ext Air Sensor A Under Temp - Event Type Multistate_Value 6 4610_1 RW
1 = Message
2 = Warning
3 = Alarm
Ext Air Sensor B Under Temp - Event Control Multistate_Value 7 4612_1 RW 1 = Disabled
2 = Enabled
Ext Air Sensor B Under Temp - Event Type Multistate_Value 8 4613_1 RW
1 = Message
2 = Warning
3 = Alarm
Ext Dew Point Over Temp - Event Control Multistate_Value 9 4616_1 RW 1 = Disabled
2 = Enabled
Ext Dew Point Over Temp - Event Type Multistate_Value 10 4617_1 RW
1 = Message
2 = Warning
3 = Alarm
Ext Air Sensor A Issue - Event Control Multistate_Value 11 4619_1 RD 1 = Disabled
2 = Enabled
Ext Air Sensor A Issue - Event Type Multistate_Value 12 4620_1 RW
1 = Message
2 = Warning
3 = Alarm
Ext Air Sensor B Issue - Event Control Multistate_Value 13 4622_1 RD 1 = Disabled
2 = Enabled
Ext Air Sensor B Issue - Event Type Multistate_Value 14 4623_1 RW
1 = Message
2 = Warning
3 = Alarm
Chilled Water
Supply CW Over Temp - Event Control Mul tistate_Value 25 4627_1 RD 1 = Disabled
2 = Enabled
Supply CW Over Temp - Event Type Multistate_Value 26 4628_1 RW
1 = Message
2 = Warning
3 = Alarm
Supply CW Temp Sensor Issue - Event Control Multistate_Value 27 4630_1 RD 1 = Disabled
2 = Enabled
Supply CW Temp Sensor Issue - Event Type Multistate_Value 28 4631_1 RW
1 = Message
2 = Warning
3 = Alarm
Chilled Water Cntrl Valve Pos - Event Control Multistate_Value 29 4704_1 RW 1 = Disabled
2 = Enabled
Chilled Water Cntrl Valve Pos - Event Type Multistate_Value 30 4705_1 RW
1 = Message
2 = Warning
3 = Alarm