Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert® IntelliSlot® Modbus/BACnet IP 108
Subfeed 64
Subfeed Current Ix 35879 1 A AC
Subfeed Current Iy 35880 1 A AC
Subfeed Current Iz 35881 1 A AC
Subfeed Neutral Current 35882 1 A AC
Subfeed Ground Current 35883 1 10 A AC
Subfeed Output Power (kVA) 35884 1 kVA
Subfeed Output Power (kW) 35885 1 kW
Subfeed Output kW-Hrs 35886 45886 2 10 kWH
Subfeed Power Factor 35888 1 100
Subfeed Output Percent Load 35889 1 - %
Subfeed Current Ix THD 35890 1 10 %
Subfeed Current Iy THD 35891 1 10 %
Subfeed Current Iz THD 35892 1 10 %
Subfeed Current Ix Crest Factor 35893 1 10
Subfeed Current Iy Crest Factor 35894 1 10
Subfeed Current Iz Crest Factor 35895 1 10
System
System Status 35899 1
1 = Normal Operation
2 = Startup
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
System Event Acknowledge/Reset 45900 1 2 = Reset
4 = Acknowledge
System Date and Time 39 998 49998 2
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 36 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Input and Holding (continued)
Controller Liebert iCOM® v4
Liebert Products Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units