Modbus 485 and Modbus IP Protocols - UPS Systems
157 Liebert® IntelliSlot® Modbus/BACnet IP
Configuration Description 30497 1
0 = Single Module System 33
1 = Single Module System 34
2 = Single Module System 44
3 = 1+1 33
4 = 1+1 34
5 = 1+1 44
6 = 1+N 33 7 = 1+N 34
8 = 1+N 44
9 = N+1 33
10 = N+1 34
11 = N+1 44
12 = SCC w/Continuous Duty SS 33
13 = SCC w/
Continuous Duty
SS 44
14 = SCC w/
Momentary
Duty SS
15 = Main Static
Switch
SCC, N+1,
1+N,
1+1, SMS
System Accumulated Energy 30810 40810 2 10 Units: kWH SCC, 1+N,
N+1
Module Accumulated Energy 30812 40812 10 Units: kWH SMS, 1+N,
N+1, SCC
Output kWh Reset Timestamp 30814 2 Secs since Epoch(UTC) SMS, 1+N,
N+1, SCC
Output Peak kW Demand 30816 Units: kWH SMS, 1+N,
N+1, SCC
Output Peak kW Demand Hist 30817 1 Uni ts: kW SMS, 1+N,
N+1, SCC
Peak kW Demand Period 30818 1
1 = Hourly
2 = Daily
3 = Weekly
4 = Monthly
5 = Yearly
SMS, 1+N,
N+1, SCC
Peak kW Demand Timestamp 30819 2 Secs since Epoch(UTC) SMS, 1+N,
N+1, SCC
Ratings
System UPS Module Count 30501 1 SCC, 1+N,
1+1, SMS
MultiModule
Multi-module System Output Voltage
RMS A-B 30505 1 Units : VAC 1+N, SCC
Multi-module System Output Voltage
RMS B-C 30506 1 Units : VAC 1+N, SCC
Multi-module System Output Voltage
RMS C-A 30507 1 Units : VAC 1+N, SCC
Multi-module System Output Voltage
RMS A-N 30508 1 Units : VAC 1+N, SCC
Multi-module System Output Voltage
RMS B-N 30509 1 Units : VAC 1+N, SCC
Multi-module System Output Voltage
RMS C-N 30510 1 Units : VAC 1+N, SCC
Sum of MMS Output RMS Currents
for Phase A 30511 1 Units : A AC 1+N, SCC
Table 56 Liebert NXL - 60Hz, UL version (Model 40) - Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Regs Scale Units / Notes
NXL
Types