BACnet Communications - Thermal Management Products
297 Liebert® IntelliSlot® Modbus/BACnet IPTable 96 Liebert DataMate, Liebert Mini-Mate2 - MM2
Controller MM2
Liebert Products Liebert DataMate
Liebert Mini-Mate2
Data Description BACnet Instance Notes
Status Points (View)
Temperature BS01_x
Humidity BS02_x
Cooling BS03_x 1=On / 0=Off
Heating BS04_x 1=On / 0=Off
Humidification BS05_x 1=On / 0=Off
Dehumidification BS06_x 1=On / 0=Off
Econ-o-Cycle BS0 7_x 1=On / 0=Off
Stages BS08_x —
% Capacity BS09_x
Unit On/Off BS18_x 1=On / 0=Off
Alarm Points
Communications BA01_x:00
Local Off BA01_x:01
Remote Off BA01_x:02
High Head Pressure 1 BA01_x:03
Loss of Airflow BA01_x:05
Standby Glycol Unit On BA01_x:06
Change Filters BA01_x:07
High Temperature BA01_x:08
Low Temperature BA01_x:09
High Humidity BA02_x:00
Low Humidity BA02_x:01
Humidifier Problem BA02_x:02
Smoke Detected BA02_x:08
Loss of Water Flow BA02_x:09
Standby Unit On BA02_x:10
Short Cycle BA03:01
Loss of Power BA03:02
Local Alarm 1 BA03:06
Local Alarm 2 BA03:07
High Water BA03:08
Local Alarm 4 BA03:09
Setpoints (View)
Temperature BS10_x
Humidity BS12_x
Control Points (Set)
Remote On/Off BC01_x Bit 0 On=unit Off; Bit 1 On=unit On
Temperature Setpoint BC02_x
Humidity Setpoint BC03_x