BACnet Communications - Thermal Management Products
235 Liebert® IntelliSlot® Modbus/BACnet IP
Fluid 1
Fluid Input Temperature Analog_Value 871 5897_1 RD Units: deg C 6
Fluid Input Temperature Analog_Value 10871 5897_1_deg_F RD Units: deg F 6
Fluid Output Temperature Analog_Value 872 5898_1 RD Units: deg C 6
Fluid Output Temperature Analog_Value 10872 5898_1_deg_F RD Units: deg F 6
Fluid 2
Fluid Input Temperature Analog_Value 1871 5897_2 RD Units: deg C 6
Fluid Input Temperature Analog_Value 11871 5897_2_deg_F RD Units: deg F 6
Fluid Output Temperature Analog_Value 1872 5898_2 RD Units: deg C 6
Fluid Output Temperature Analog_Value 11872 5898_2_deg_F RD Units: deg F 6
Circuit
Fluid Flow Rate Analog_Value 881 5899_1 RD Units: l/min 6
Circuit 2
Fluid Flow Rate Analog_Value 891 5899_2 RD Units: l/min 6
System Operations - Cooling Load 1
Circuit Cooling Load Analog_Value 901 5905_1 _1 RD Units: kW 6
System Operations - Cooling Load 2
Circuit Cooling Load Analog_Value 911 5905_1 _2 RD Units: kW 6
Table 79 Extra Notes to Table78
Number Description
1This point is supported on:
iCOM controller version 1.04.042.STD
2
This point is supported on:
iCOM controller version 2.00.11R for US
iCOM controller version 2.00.12R (for Japan and China – language corrections only)
3This point is supported on:
iCOM controller version 2.01.23R
4This point is supported on:
iCOM controller version 2.02.16R
5This point is supported on:
iCOM controller version 2.03.27.07R
6This point is supported on:
iCOM controller version 2.01.32.02R
Table 78 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3,
Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Analog Data (continued)
Data Label Object Type
Instanc
eObject Name
Acces
sNotes
Extra
Notes