Modbus 485 and Modbus IP Protocols - Thermal Management Products
67 Liebert® IntelliSlot® Modbus/BACnet IP
XD System 4 Secondary Fans
Fan State 31137 1
0 = off
1 = on
2 = economy
Fan Economy Mode 31138 41138 1
0 = disabled
1 = automatic
2 = manual
XD System 5 Temperature Sensor 1
Remote Sensor Temperature 31144 1 10 Units : deg C
Remote Sensor Temperature 31145 1 10 Units : deg F
XD System 5 Temperature Sensor 2
Remote Sensor Temperature 31151 1 10 Units : deg C
Remote Sensor Temperature 31152 1 10 Units : deg F
XD System 5 Temperature Sensor 4
Remote Sensor Temperature 31165 1 10 Units : deg C
Remote Sensor Temperature 31166 1 10 Units : deg F
XD System 5 Secondary Fans
Fan State 31172 1
0 = off
1 = on
2 = economy
Fan Economy Mode 31173 41173 1
0 = disabled
1 = automatic
2 = manual
XD System 6 Temperature Sensor 1
Remote Sensor Temperature 31179 1 10 Units : deg C
Remote Sensor Temperature 31180 1 10 Units : deg F
XD System 6 Temperature Sensor 2
Remote Sensor Temperature 31186 1 10 Units : deg C
Remote Sensor Temperature 31187 1 10 Units : deg F
XD System 6 Temperature Sensor 4
Remote Sensor Temperature 31200 1 10 Units : deg C
Remote Sensor Temperature 31201 1 10 Units : deg F
XD System 6 Secondary Fans
Fan State 31207 1
0 = off
1 = on
2 = economy
Fan Economy Mode 31208 41208 1
0 = disabled
1 = automatic
2 = manual
XD System 7 Temperature Sensor 1
Remote Sensor Temperature 31214 1 10 Units : deg C
Remote Sensor Temperature 31215 1 10 Units : deg F
XD System 7 Temperature Sensor 2
Remote Sensor Temperature 31221 1 10 Units : deg C
Remote Sensor Temperature 31222 1 10 Units : deg F
XD System 7 Temperature Sensor 4
Remote Sensor Temperature 31235 1 10 Units : deg C
Remote Sensor Temperature 31236 1 10 Units : deg F
Table 21 Liebert XDP - Input and Holding (continued)
Data Label Input Holding # of Reg Scale Notes/Units