BACnet Communications - Thermal Management Products
227 Liebert® IntelliSlot® Modbus/BACnet IPTable 78 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Analog Data
Data Label Object Type
Instanc
eObject Name
Acces
sNotes
Extra
Notes
Air
Air Temperature Set Point Analog_Value 1 5008_1 RW Units: deg C 1, 2, 3,
4, 5, 6
Air Temperature Set Point Analog_Value 10001 5008_1_deg_F RW Units: deg F 1, 2, 3,
4, 5, 6
Air Temperature Proportional
Band Analog_Value 2 5325_1 RW Units: deg C 1, 2, 3,
4, 5, 6
Air Temperature Proportional
Band Analog_Value 10002 5325_1_deg_F RW Units: deg F 1, 2, 3,
4, 5, 6
Air Temperature Dead Band Analog_Value 3 5011_1 RW Units: deg C 1, 2, 3,
4, 5, 6
Air Temperature Dead Band Analog_Value 10003 5011_1_deg_F RW Units: deg F 1, 2, 3,
4, 5, 6
Air Temperature Control
Integration Time Analog_Value 4 5326_1 RW Units: min 1, 2, 3,
4, 5, 6
Today's High Air Temperature Analog_Value 5 5327_1 RD Units: deg C 1, 2, 3,
4, 5, 6
Today's High Air Temperature Analog_Value 10005 5327_1_deg_F RD Units: deg F 1, 2, 3,
4, 5, 6
Today's High Air Temperature
Time Analog_Value 6 5328_1 RD Un its: Seconds
since Midnight
1, 2, 3,
4, 5, 6
Today's Low Air Temperature Analog_Value 7 5329_1 RD Units: deg C 1, 2, 3,
4, 5, 6
Today's Low Air Temperature Analog_Value 10007 5329_1_deg_F RD Units: deg F 1, 2, 3,
4, 5, 6
Today's Low Air Temperature
Time Analog_Value 8 5330_1 RD Un its: Seconds
since Midnight
1, 2, 3,
4, 5, 6
Air - Supply Air
Supply Air Temperature Analog_Value 19 5002_1_1 RD Units: deg C 1, 2, 3,
4, 5, 6
Supply Air Temperature Analog_Value 10019 5002_1_1_deg
_F RD Units: deg F 1, 2, 3,
4, 5, 6
Supply Air Temperature Set
Point Analog_Value 20 53 31_1_1 RW Units: deg C 1
Supply Air Temperature Set
Point Analog_Value 10020 5331 _1_1_deg
_F RW Units: deg F 1
Supply Air Over Temp Threshold Analog_Value 21 5014_1_1 RW Units: deg C 2, 3, 4,
5, 6
Supply Air Over Temp Threshold Analog_Value 10021 5014_1_1_deg
_F RW Units: deg F 2, 3, 4,
5, 6
Supply Air Under Temp
Threshold Analog_Value 22 5018_1_1 RW Units: deg C 2, 3, 4,
5, 6
Supply Air Under Temp
Threshold Analog_Value 100 22 5018_1_1_deg
_F RW Units: deg F 2, 3, 4,
5, 6
Air - Return Air
Return Air Temperature Analog_Value 31 4291_1_1 RD Units: deg C 1, 2, 3,
4, 5, 6
Return Air Temperature Analog_Value 10031 4291_1_1_deg
_F RD Units: deg F 1, 2, 3,
4, 5, 6
Return Air Temperature Set
Point Analog_Value 32 53 33_1_1 RW Units: deg C 1