Modbus 485 and Modbus IP Protocols - UPS Systems
139 Liebert® IntelliSlot® Modbus/BACnet IPTable 50 Liebert Nfinity® - Status and Coil
Data Description Status Coil
Number
of Bits Scale Notes / Units
Automatic Battery Test Enabled 10003 3 1
Battery Charger On 10044 1
Inverter Ready 10047 1
Power Factor Correction State 10050 1
Load on Inverter 10073 1
Bypass Active 10074 1
Replace Battery 10081 1
Battery Under Test 10082 1
Load on Battery 10128 1
Load on Bypass 10129 1
Load on Manual Bypass 10132 1
Load Transferred to Bypass Due to UPS Fault 10134 1
Transfer Inhibit 10146 1
Output Off Pending 10151 1
Low Battery - Shutdown Imminent 10152 1
Output Overload 10154 1
UPS Overload 10155 1
Output Off 10158 1
Check Air Filter - Replace 10170 1
Transformer Over Temperature 10178 1
Input Power Supply Fail 10186 1
Internal Device Communication Failure 10284 1
Device Active Alarm 10290 1
Main Control Warning 10291 1
Redundant Control Warning 10292 1
Control Module Failure 10293 1
Redundant Control Module Failed 10294 1
User Interface Module Failed 10295 1
UPS Power Not Redundant 10296 1
Power Module Failure 1029 8 1
Battery Module Failure 10299 1
Power Module Warning 10300 1
Battery Module Warning 10301 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.