Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 58Table 18 Liebert XDC - Status and Coil
Controller Liebert iCOM® v4
Data Description Status Coil
Number
of Bits Scale Notes / Units
Pump 1 Loss of Flow 10001 1 Active on Alarm
Pump 2 Loss of Flow 10002 1 Active on Alarm
Fan Issue 10003 1 Active on Alarm
System Condensation Detected 10004 1 Active on Alarm
Customer Input 1 10005 1 Active on Alarm
Supply Refrigerant Over Temp 10006 1 Active on Alarm
Supply Refrigerant Under Temp 10007 1 Active on Alarm
Supply Refrigerant Temp Sensor Issue 10008 1 Active on Alarm
Ext Air Sensor A Over Temperature 10009 1 Active on Alarm
Ext Air Sensor A Under Temperature 10010 1 Active on Alarm
Ext Air Sensor A Issue 10011 1 Active on Alarm
Ext Air Sensor B Over Temperature 10012 1 Active on Alarm
Ext Air Sensor B Under Temperature 10013 1 Active on Alarm
Ext Air Sensor B Issue 10014 1 Active on Alarm
Ext Dew Point Over Temperature 10015 1 Active on Alarm
Pump Short Cycle 10016 1 Active on Alarm
Compressor 1A High Head Pressure 10017 1 Active on Alarm
Compressor 1B High Head Pressure 10018 1 Active on Alarm
Compressor 2A High Head Pressure 10019 1 Active on Alarm
Compressor 2B High Head Pressure 10020 1 Active on Alarm
Compressor 1A Short Cycle 10021 1 Active on Alarm
Compressor 1B Short Cycle 10022 1 Active on Alarm
Compressor 2A Short Cycle 10023 1 Active on Alarm
Compressor 2B Short Cycle 10024 1 Active on Alarm
Circuit 1 Low Suction Pressure 10025 1 Active on Alarm
Circuit 2 Low Suction Pressure 10026 1 Active on Alarm
Shutdown - Loss Of Power 10027 �� 1 Active on Alarm
Smoke Detected 10028 1 Active on Alarm
Water Under Floor 10029 1 Active on Alarm
Service Required 10030 1 Active on Alarm