BACnet Communications - UPS Systems
Liebert® IntelliSlot® Modbus/BACnet IP 318
Output Amp Over User Limit-Phs A Binary_Value 91 4286_1 RD Active on Alarm SMS, 1+N,
SCC
Output Amp Over User Limit-Phs B Binary_Value 92 4287_1 RD Active on Alarm SMS, 1+N,
SCC
Output Amp Over User Limit-Phs C Binary_Value 93 4288_1 RD Active on Alarm SMS, 1+N,
SCC
System Output Fault Binary_Value 94 4389_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Output Of/Uf Binary_Value 95 5144_1 RD Active on Alarm SMS, 1+N,
N+1
Inverter
Inverter Failure Binary_ Value 106 4233_1 RD Active on Alarm SMS, 1+N,
N+1
Inverter Overload Phase A Binary_Value 107 4234_1 RD Active on Alarm SMS, 1+N,
N+1
Inverter Overload Phase B Binary_Value 108 4235_1 RD Active on Alarm SMS, 1+N,
N+1
Inverter Overload Phase C Binary_Value 109 4236_1 RD Active on Alarm SMS, 1+N,
N+1
Inverter Inhibit - External Binary_Value 110 4237_1 RD Active on Alarm SMS, 1+N,
N+1
Inverter Shutdown - Overload Binary_Value 111 4290_1 RD Active on Alarm SMS, 1+N,
N+1
Inverter Off - External Binary_Value 112 4390_1 RD Active on Alarm CE models
only
Inverter Static Switch SCR Short Binary_Value 113 4391_1 RD Active on Alarm CE models
only
Environment
Inlet Air Over Temperature Binary_Value 124 4294_1 RD Active on Alarm SMS, 1+N,
N+1
Outlet Air Overtemperature Limit Binary_Value 125 5768_1 RD Active on Alarm SMS, 1+N,
N+1
Equipment Temperature Sensor Fail Binary_Value 126 4747_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Equipment Over Temperature Binary_Value 127 4310_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
External Input Signals
Input Contact 01 Binary_Value 138 4270_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Input Contact 02 Binary_Value 139 4271_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Input Contact 03 Binary_Value 140 4272_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Input Contact 04 Binary_Value 141 4273_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Input Contact 05 Binary_Value 142 4274_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Input Contact 06 Binary_Value 143 4275_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Input Contact 07 Binary_Value 144 4276_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Input Contact 08 Binary_Value 145 4277_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Table 106 Liebert NXL- 60Hz, UL version (Model 40) - Binary Data (continued)
Data Label
Object
Type Instance
Object
Name Access Notes
Liebert
NXL Type