BACnet Communications - Thermal Management Products
237 Liebert® IntelliSlot® Modbus/BACnet IP
Fan Control Mode MultiState_Value 82 5373_1 RW
1 = Auto
2 = Manual
3 = Economy
4 = Delta
1
Fan Control Sensor MultiState_Value 83 5586_1 RW
1 = Supply
2 = Remote
3 = Return
4 = Manual
2, 3, 4,
5, 6
System Info
System Status MultiState_Value 93 4123_1 RD
1 = Normal
Operation
2 = StartUp
3 = Normal with
Warning
4 = Normal with
Alarm
5 = Abnormal
Operation
1, 2, 3,
4, 5, 6
System Operating State MultiState_Value 94 4706_1 RD
1 = off
2 = on
3 = standby
1, 2, 3,
4, 5, 6
System Control Mode MultiState_Value 95 4707_1 RD
1 = Internal (Auto)
2 = External
(Manual)
1, 2, 3,
4, 5, 6
System Operating State
Reason MultiState_Value 96 5074_1 RD
1 = Reason
Unknown
2 = Network
Display
3 = Alarm
4 = Schedule
5 = Remote
System
6 = External Input
7 = Local Display
1, 2, 3,
4, 5, 6
System Operations
Fan State MultiState_Value 107 5381_1 RD 1 = off
2 = on
1, 2, 3,
4, 5, 6
Cooling State MultiState_Value 108 5382_1 RD 1 = off
2 = on
1, 2, 3,
4, 5, 6
Free Cooling State MultiState_Value 109 5383_1 RD 1 = off
2 = on
1, 2, 3,
4, 5, 6
Maintenance Tracking State MultiState_Value 110 5384_1 RD 1 = off
2 = on
1, 2, 3,
4, 5, 6
Hot Water / Hot Gas State MultiState_Value 111 5385_1 RD 1 = off
2 = on
1, 2, 3,
4, 5, 6
Electric Reheat State MultiState_Value 112 5386_1 RD 1 = off
2 = on
1, 2, 3,
4, 5, 6
Dehumidifier State MultiState_Value 113 5387_1 RD 1 = off
2 = on
1, 2, 3,
4, 5, 6
Humidifier State MultiState_Value 114 5388_1 RD 1 = off
2 = on
1, 2, 3,
4, 5, 6
System On/Off Control MultiState_Value 115 5143_1 RW 1 = off
2 = on
1, 2, 3,
4, 5, 6
Table 80 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3,
Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Multistate Data (continued)
Data Label Object Type Instance Object Name Access Notes
Extra
Notes