BACnet Communications - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 288
Sensor Issue - Event Type Multistate_Value 812 5499_20 RW
1 = Message
2 = Warning
3 = Alarm
Ext Remote Shutdown - Event Control Multistate_Value 813 5501_20 RW 1 = Disabled
2 = Enabled
Ext Remote Shutdown - Event Type Multistate_Value 814 5502_20 RW
1 = Message
2 = Warning
3 = Alarm
XD System 20 Secondary Fans 1
Fan State Multistate_Value 825 5510_20_1 RD 1 = Off / 2 = On
3 = Economy
Fan Economy Mode Mul tistate_Value 826 5511_20_1 RW
1 = Disabled
2 = Automatic
3 = Manual
System Information
System Status Multistate_Value 837 4123_1 RD
1 = Normal Operation
2 = Startup
3 = Normal with
Warning
4 = Normal with
Alarm
5 = Abnormal
Operation
System Operating State Multistate_Value 838 4706_1 RD 1 = Off / 2 = On
3 = Standby
System Control Mode Multistate_Value 839 4707_1 RD 1 = Internal (Auto)
2 = External (Manual)
System Operating State Reason Multistate_Value 840 5074_1 RD
1 = Reason Unknown
2 = Network Display
3 = Alarm
4 = Schedule
5 = Remote System
6 = External Input
7 = Local Display
System On/Off Control Multistate_Value 841 5143_1 RW 1 = Off / 2 = On
System Event Configuration
Customer Input 1 - Event Control Multistate_Value 852 4718_1 RW 1 = Disabled
2 = Enabled
Customer Input 1 - Event Type Multistate_Value 853 4719_1 RW
1 = Message
2 = Warning
3 = Alarm
System Condensation Detected - Event Control Multistate_Value 854 471 2_1 RD 1 = Disabled
2 = Enabled
System Condensation Detected - Event Type Multistate_Value 855 4713_1 RW
1 = Message
2 = Warning
3 = Alarm
Shutdown - Loss Of Power - Event Control Multistate_Value 856 4715_1 RD 1 = Disa bled
2 = Enabled
Shutdown - Loss Of Power - Event Type Multistate_Value 857 4716_1 RW
1 = Message
2 = Warning
3 = Alarm
Smoke Detected - Event Control Multistate_Value 858 4721_1 RW 1 = Disabled
2 = Enabled
Table 94 Liebert XDP, Liebert XDC - Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label Object Type Instance
Object
Name Access Notes