Modbus 485 and Modbus IP Protocols - Battery Monitoring Products
Liebert® IntelliSlot® Modbus/BACnet IP 212
Cell to Ambient Temperature Deviation
Threshold
String 1 - 32
39123-39152 1
Scale
: x /
10
Units : deg F
Ordinal Position of String
String 1 - 32 33522-33553 1
Index of Parent Battery
String 1 - 32 33554-33585 1
Cell Entity (Cells 1 – 320)
Cell Voltage
Cell 1 - 320 33586-33905 1
Scale
: x /
1000
Units : VDC
Cell Temperature
Cell 1 - 320 33906-34225 1
Scale
: x /
10
Units : deg C
Cell Temperature
Cell 1 - 320 34226-34545 1
Scale
: x /
10
Units : deg F
Internal Resistance Value
Cell 1 - 320 34546-34865 1 Units : microOhm
Intercell Resistance Value
Cell 1 - 320 34866-35185 1 Units : microOhm
Cell Voltage Low Threshold
Cell 1 - 320 35186-35505 1
Scale
: x /
1000
Units : VDC
Cell Voltage High Threshold
Cell 1 - 320 35506-35825 1
Scale
: x /
1000
Units : VDC
Cell Temperature Low Threshold
Cell 1 - 320 35826-36145 1
Scale
: x /
10
Units : deg C
Cell Temperature Low Threshold
Cell 1 - 320 36146-36465 1
Scale
: x /
10
Units : deg F
Cell Temperature High Threshold
Cell 1 - 320 36466-36785 1
Scale
: x /
10
Units : deg C
Cell Temperature High Threshold
Cell 1 - 320 36786-37105 1
Scale
: x /
10
Units : deg F
Internal Resistance Low Threshold
Cell 1 - 320 37106-37425 1 Units : microOhm
Internal Resistance High Threshold
Cell 1 - 320 37426-37745 1 Units : microOhm
Intercell Resistance High Threshold
Cell 1 - 320 37746-38065 1 Units : microOhm
Ordinal Position of Cell
Cell 1 - 320 38066-38385 1
Index of Parent String
Cell 1 - 320 38386-38705 1
Index of Parent Battery
Cell 1 - 320 38706-39025 1
Cell Entity (Cells 321 – 360)
Cell Voltage
Cell 321 - 360 39155-39194 1
Scale
: x /
1000
Units : VDC
Table 75 Alber® BDSU - Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units