BACnet Communications - Thermal Management Products
279 Liebert® IntelliSlot® Modbus/BACnet IPTable 92 Liebert XDP, Liebert XDC - Binary Data
Controller Liebert iCOM® v4
Data Label Object Type Instance
Object
Name Access Notes
External Air
Ext Air Sensor A Over Temperature Binary_Value 1 4601_1 RD
Ext Air Sensor B Over Temperature Binary_Value 2 4604_1 RD
Ext Air Sensor A Under Temperature Binary_Value 3 4608_1 RD
Ext Air Sensor B Under Temperature Binary_Value 4 4611_1 RD
Ext Dew Point Over Temperature Binary_Value 5 4615_1 RD
Ext Air Sensor A Issue Binary_Value 6 4618_1 RD
Ext Air Sensor B Issue Binary_Value 7 4621_1 RD
Chilled Water
Supply Chilled Water Over Temp Binary_Value 18 4626_1 RD
Supply Chilled Water Temp Sensor Issue Binary_Value 19 4629_1 RD
Chilled Water Control Valve Position Binary_Value 20 4703_1 RD
Refrigerant
Supply Refrigerant Over Temp Binary_Value 31 4634_1 RD
Supply Refrigerant Under Temp Binary_Value 32 4637_1 RD
Supply Refrigerant Temp Sensor Issue Binary_Value 33 4 640_1 RD
Fluid
Supply Fluid Over Temp Bi nary_Value 44 4645_1 RD
Supply Fluid Under Temp Binary_Value 45 4648_1 RD
Supply Fluid Temp Sensor Issue Binary_Value 46 4651_1 RD
Pumps
Pump 1 Loss of Flow Binary_Value 57 4656_1 RD
Pump 2 Loss of Flow Binary_Value 58 4659_1 RD
Pump Short Cycle Binary_Value 59 4662_1 RD
Pumps - Pump Hours 1
Pump Hours Exceeded Binary_Value 70 5300_1_1 RD
Pumps - Pump Hours 2
Pump Hours Exceeded Binary_Value 81 5300_1_2 RD
Compressors
Compressor 1A High Head Pressure Binary_Value 92 4669_1 RD
Compressor 1B High Head Pressure Binary_Value 93 4672_1 RD
Compressor 2A High Head Pressure Binary_Value 94 4675_1 RD
Compressor 2B High Head Pressure Binary_Value 95 4678_1 RD
Compressor 1A Short Cycle Binary_Value 96 4681_1 RD
Compressor 1B Short Cycle Binary_Value 97 4684_1 RD
Compressor 2A Short Cycle Binary_Value 98 4687_1 RD
Compressor 2B Short Cycle Binary_Value 99 4690_1 RD
Circuit 1 Low Suction Pressure Binary_Value 100 4693_1 RD
Circuit 2 Low Suction Pressure Binary_Value 101 4696_1 RD