BACnet Communications - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 240
Clogged Air Filter - Event Type MultiState_Value 167 5136_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Ext Loss of Air Blower - Event
Control MultiState_Value 168 5393_1 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Ext Loss of Air Blower - Event
Type MultiState_Value 169 5394_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
System Event Configuration - Compressor 1
Compressor High Head
Pressure - Event Control MultiState_Value 180 5316_1_1 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Compressor High Head
Pressure - Event Type MultiState_Value 181 5317_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Compressor Low Suction
Pressure - Event Control MultiState_Value 182 5318_1_1 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Compressor Low Suction
Pressure - Event Type MultiState_Value 183 5319_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Compressor Pump Down Issue
- Event Control MultiState_Value 184 5395_1_1 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Compressor Pump Down Issue
- Event Type MultiState_Value 185 5396_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Compressor Short Cycle -
Event Control MultiState_Value 186 5397_1_1 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Compressor Short Cycle -
Event Type MultiState_Value 187 5398_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Compressor Thermal Overload
- Event Control MultiState_Value 188 5320_1_1 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Compressor Thermal Overload
- Event Type MultiState_Value 189 5321_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Dig Scroll Comp Discharge
Over Temp - Event Ctrl MultiState_Value 190 5399_1_1 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Dig Scroll Comp Discharge
Over Temp - Event Type MultiState_Value 191 5400_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
System Event Configuration - Compressor 2
Compressor High Head
Pressure - Event Control MultiState_Value 202 5316_1_2 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Compressor High Head
Pressure - Event Type MultiState_Value 203 5317_1_2 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Compressor Low Suction
Pressure - Event Control MultiState_Value 204 5318_1_2 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Compressor Low Suction
Pressure - Event Type MultiState_Value 205 5319_1_2 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Compressor Pump Down Issue
- Event Control MultiState_Value 206 5395_1_2 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Table 80 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3,
Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Multistate Data (continued)
Data Label Object Type Instance Object Name Access Notes
Extra