BACnet Communications - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 258
Unit Partial Shutdown Binary_Value 237 5112_1 RD Active on Alarm
Unit Shutdown Binary_Value 238 5113_1 RD Active on Alarm
Water Leakage Detector Sensor Issue Binary_Value 239 5114_1 RD Active on Alarm
BMS Communications Timeout Binary_Value 240 5115_1 RD Active on Alarm
Maintenance Due Binary_ Value 241 5116_1 RD Active on Alarm
Maintenance Completed Binary_Value 242 5117_1 RD Active on Alarm
Clogged Air Filter Binary_Value 243 5118_1 RD Active on Alarm
RAM Battery Issue Binary_Value 244 5119_1 RD Active on Alarm
Master Unit Communication Lost Binary_Value 245 5120_1 RD Active on Alarm
High Power Shutdown Binary_Value 246 5121_1 RD Active on Alarm
Supply Fluid Temp Sensor Issue Binary_Value 247 4651_1 RD Active on Alarm
GlobalCondenser
Condenser Outside Air Temp Sensor Issue Binary_Value 259 5535_1 RD Active on Alarm
Condenser Outside Air Temp Out of Operating
Range Binary_Value 260 5536_1 RD Active on Alarm
Condenser Control Board Issue Binary_Value 261 5537_1 RD Active on Alarm
Condenser Refrigerant Pressure Over Threshold Binary_Value 262 5539_1 RD Active on Alarm
Condenser Refrigerant Pressure Under
Threshold Binary_Value 263 5540_1 RD Active on Alarm
Condenser Refrigerant Pressure Sensor Issue Binary_Value 264 5541_1 RD Active on Alarm
GlobalCondenser - GC Fan 1
Condenser Fan Issue Binary_Value 280 5277_1_1 RD Active on Alarm
GlobalCondenser - GC Fan 2
Condenser Fan Issue Binary_Value 292 5277_1_2 RD Active on Alarm
Table 83 Liebert CRV - Binary Data (continued)
Controller Liebert iCOM® v4
Data Label Object Type Instance
Object
Name Access Notes