Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 52
Condensers 4
Condenser Fan Speed 30417 1 Units: %
Uint16 1, 2
Fluid
Fluid Pressure 30418 1 10 Units: bar
Int16 1, 2
Fluid Cooling Proportional Band 30419 40419 1 10 Units: deg C
Uint16 1, 2
Fluid Cooling Proportional Band 30420 40420 1 10 Units: deg F
Uint16 1, 2
Supply (Outlet) Fluid
Supply Fluid Temp Set Point 1 30424 40424 1 10 Units: deg C
Int16 1, 2
Supply Fluid Temp Set Point 1 30425 40425 1 10 Units: deg F
Int16 1, 2
Supply Fluid Temp Set Point 2 30426 40426 1 Units: deg C
Int16 1, 2
Supply Fluid Temp Set Point 2 30427 40427 1 Units: deg F
Int16 1, 2
Supply Fluid Over Temp Alarm Threshold 30430 40430 1 Units: deg C
Int16 1, 2
Supply Fluid Over Temp Alarm Threshold 30431 40431 1 Units: deg F
Int16 1, 2
Supply Fluid Under Temp Alarm Threshold 30434 40434 1 Units: deg C
Int16 1, 2
Supply Fluid Under Temp Alarm Threshold 30435 40435 1 Units: deg F
Int16 1, 2
Pump 1
Pump Hours 30450 40450 1 Units: hr
Uint16 1, 2
Pump Hours Threshold 30451 40451 1 Units: hr
Uint16 1, 2
Pump 2
Pump Hours 30455 40455 1 Units: hr
Uint16 1, 2
Pump Hours Threshold 30456 40456 1 Units: hr
Uint16 1, 2
Free Cooling
Free Cooling External Temperature Delta 30460 40460 1 Units: deg C
Uint16 1, 2
Free Cooling External Temperature Delta 30461 40461 1 Units: deg F
Uint16 1, 2
Free Cooling Status 30462 1
0 = off
2 = on
3 = No Support
1, 2
Free Cooling Valve Open Position 30463 1 Units: %
Uint16 1, 2
Free Cooling Valve Hours 30464 40464 1 Units: hr
Uint16 1, 2
Free Cooling Valve Hours Threshold 30465 40465 1 Units: hr
Uint16 1, 2
Table 15 Liebert HPC (Chiller) - Input and Holding (continued)
Controller Liebert iCOM® v4
Data Label Input Holding
# of
Reg Scale Notes/Units
Extra
Notes