BACnet Communications - UPS Systems
317 Liebert® IntelliSlot® Modbus/BACnet IP
Battery Self Test Binary_Value 46 4741_1 RD Active on Alarm SMS, 1+N,
N+1
Main Battery Disconnect Open Binary_Value 47 4173_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Low Binary_Value 48 4162_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Temperature Sensor Fault Binary_Value 49 41 74_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Charging Inhibited Binary_Value 50 4200_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Circuit Breaker 1 Open Binary_Value 51 4176_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Circuit Breaker 2 Open Binary_Value 52 4179_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Circuit Breaker 3 Open Binary_Value 53 4182_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Circuit Breaker 4 Open Binary_Value 54 4185_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Circuit Breaker 5 Open Binary_Value 55 4188_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Circuit Breaker 6 Open Binary_Value 56 4191_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Circuit Breaker 7 Open Binary_Value 57 4194_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Circuit Breaker 8 Open Binary_Value 58 4197_1 RD Active on Alarm SMS, 1+N,
N+1
Battery - External Monitor 1 Binary_Value 59 4220_1 RD Active on Alarm SMS, 1+N,
N+1
Battery - External Monitor 2 Binary_Value 60 4221_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Ground Fault Binary_Value 61 42 22_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Low Shutdown Binary_Value 62 4742_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Over Temperature Binary_Value 63 4219_1 RD Active on Alarm SMS, 1+N,
N+1
Battery Test Failed Binary_Value 64 4323_1 RD Active on Alarm SMS, 1+N,
N+1
DC Bus
DC Bus Ground Fault - Positive Binary_Value 75 4308_1 RD Active on Alarm SMS, 1+N,
N+1
DC Bus Ground Fault - Negative Binary_Value 76 4309_1 RD Active on Alarm SMS, 1+N,
N+1
Output
System Shutdown - EPO Binary_Value 87 4213_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
System Shutdown - REPO Binary_Value 88 4214_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
System Output Off Binary_Value 89 4215_1 RD Active on Alarm SMS, 1+N,
N+1
System Output Low Power Factor Binary_Value 90 4230_1 RD Active on Alarm SMS, 1+N,
N+1
Table 106 Liebert NXL- 60Hz, UL version (Model 40) - Binary Data (continued)
Data Label
Object
Type Instance
Object
Name Access Notes
Liebert
NXL Type