Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert® IntelliSlot® Modbus/BACnet IP 196
Bypass Current L2 30210 1 A
Output Voltage L2 30213 1 V
Output Current L2 30214 1 A
Input Voltage L3 30253 1 V
Input Current L3 30254 1 A
Bypass Voltage L3 30259 1 V
Bypass Current L3 30260 1 A
Output Voltage L3 30263 1 V
Output Current L3 30264 1 A
Black Out Count 30301 1
Brown Out Count 30302 1
Transient Count 30301 1
Silent Audible Alarm 40101 Any value
Battery Start 40102 1 1=Start, 0=Abort
Open UPS Output Switch 40104 Delay time in Seconds, last digit wil l be
ignored
Reboot UPS Output Switch 40105 1 Delay time in Seconds, last digit will be
ignored
Close UPS Output Switch 40106 Delay time in Seconds, last digit will be
ignored
Transfer Load to Bypass 40107 1 Any value
Transfer Load to Inverter 40108 Any value
Reset UPS Statistic data 40111 1 Any value
Turn UPS Outlets On 40112 1 Bitmap mask for Outlet 1-16. All bits set to 1
will be turned On
Turn UPS Outlets Off 40113 1 Bitmap mask for Outlet 1-16. All bits set to 1
will be turned Off
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 66 Liebert Series 300 UPS - Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units