Modbus 485 and Modbus IP Protocols - UPS Systems
189 Liebert® IntelliSlot® Modbus/BACnet IP
System Output Nominal Voltage The nominal (or rated) system output voltage
System Output Pct Power Phase A The system output power on phase A as a percentage of the rated capacity
System Output Pct Power Phase B The system output power on phase B as a percentage of the rated capacity
System Output Pct Power Phase C The syste m output power on phase C as a percentage of the rated capacity
System Output Pct Pwr (VA) Phs A The system output apparent power on phase A as a percentage of the rated capacity
System Output Pct Pwr (VA) Phs B The system output apparent power on phase B as a percentage of the rated capacity
System Output Pct Pwr (VA) Phs C The system output apparent power on phase C as a percentage of the rated capacity
System Output Power Factor Phs A The system output power factor of phase A
System Output Power Factor Phs B The system output power factor of phase B
System Output Power Factor Phs C The system output power factor of phase C
System Output Power The sum total power of all system output phases
System Output RMS Current Phs A The system output RMS current for Phase A
System Output RMS Current Phs B The system output RMS current for Phase B
System Output RMS Current Phs C The system output RMS current for Phase C
System Output Voltage RMS A-B The system output RMS voltage between phases A and B
System Output Voltage RMS A-N The system output RMS voltage between phases A and Neutral
System Output Voltage RMS B-C The system output RMS voltage between phases B and C
System Output Voltage RMS B-N The system output RMS voltage between phases B and Neutral
System Output Voltage RMS C-A The system output RMS voltage between phases C and A
System Output Voltage RMS C-N The syste m output RMS voltage between phases C and Neutral
System Redundant UPS Modules Number of redundant UPS modules in the system
System Shutdown - EPO System shutdown due to Emergency Power Off (EPO)
System Shutdown - REPO System shutdown due to Remote Emergency Power Off (REPO)
System Status The operating status for the system
System UPS Module Count Number of UPS modules in the system
The main battery disconnect status. Main Battery Disconnect Status
Time Remaining - ECO Mode Time remaining before current active ECO Mode session stops.
Total System Operating Time The cumulative operation time of the unit
Trap Filter Disconnect Trap filter disconnect
Unexpected Main Battery
Disconnect Closure The main battery disconnect has cl osed unexpectedly.
UPS Battery Status UPS battery status
UPS Module Type UPS module type
UPS Output on Bypass The ou tput power is supplied by the bypass
UPS Output Source UPS output source
UPS System Output Source The UPS system's output power source
Vdc Backfeed The voltage between battery and DC bus measurements is out of tolerance.
Table 60 Liebert NXL - 50Hz, CE version (Models 48 and 49) - Glossary
Data Label Data Description