Modbus 485 and Modbus IP Protocols - UPS Systems
175 Liebert® IntelliSlot® Modbus/BACnet IP
Output Wire Configuration 30556 1
0 = Two Wire (single phase +
return)
1 = Two Wire (2 phase, no
neutral)
2 = Three Wire (2 phase +
neutral)
3 = Three Wire (3 phase, no
neutral)
4 = Four Wire (3 phases +
neutral)
Static Switch Type 30557 1
0 = Not Applicable
1 = Continuous Duty
2 = Momentary Duty
Configuration Description 30558 1
0 = Single Module System 33
1 = Single Module System 34
2 = Single Module System 44
3 = 1+1 33
4 = 1+1 34
5 = 1+1 44
6 = 1+N 33
7 = 1+N 34
8 = 1+N 44
9 = N+1 33
10 = N+1 34
11 = N+1 44
12 = SCC w/Continuous Duty
SS 33
13 = SCC w/Continuous Duty
SS 44
14 = SCC w/Momentary Duty
SS
15 = Main Static Switch
UPS System Output Source 30559 1
0 = None
1 = Inverter
2 = Bypass
System Input Power Source 30560 1
0 = None
1 = Utility (mains)
2 = Generator
System Status 30561 1
1 = Normal Operation
2 = StartUp
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
UPS Output Source 30562 1
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
System Fan Status 30563 1
0 = Unknown
1 = Normal
2 = Failure
System Fan Redundant Status 30564 1
0 = Unknown
1 = Redundancy Available
2 = Loss of Redundancy
System Fan Capacity Status 30565 1
0 = Unknown
1 = Normal
2 = Failure
Table 59 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) - Input and Holding
Data Label Input Holding # of Reg Scale Notes/Units