Modbus 485 and Modbus IP Protocols - Thermal Management Products
57 Liebert® IntelliSlot® Modbus/BACnet IP
Reheat Utilization Present reheating utilization expressed as a percentage of the maximum rated
capacity.
Return Fluid Over Temp Alarm
Threshold Threshold value used to generate a [Return Fluid Over Temp] alarm.
Return Fluid Over Temp Warning
Threshold Threshold value used to generate a [Return Fluid Over Temp] warning.
Return Fluid Over Temp [Return Fluid Temperature] has exceeded a specified threshold.
Return Fluid Temp Sensor Issue The return fluid temperature sensor is disconnected or the signal is out of range.
Return Fluid Temperature Fluid temperature measured at the inlet of the unit.
Return Fluid Under Temp Alarm
Threshold Threshold value used to generate a [Return Fluid Under Temp] alarm.
Return Fluid Under Temp Warning
Threshold Threshold value used to generate a [Return Fluid Under Temp] warning.
Return Fluid Under Temp [Return Fluid Temperature] has dropped below a specified threshold.
Server Class The general classification for this system
Standby Units The number of standby units.
Subgroup Event Occurred During
Communication Loss
While subgroup unit communication was lost, an event occurred on the subgroup unit.
Please check subgroup unit event log.
Supply Brine Temp Set Point Desired brine fluid temperature at the outlet of the unit.
Supply Fluid Over Temp Alarm
Threshold Threshold value used to generate a [Supply Fluid Over Temp] alarm.
Supply Fluid Over Temp Warning
Threshold Threshold value used to generate a [Supply Fluid Over Temp] warning.
Supply Fluid Over Temp [Suppl y Fluid Temperature] has exceeded a specified threshold.
Supply Fluid Temp Sensor Issue The supply fluid temperature sensor is disconnected or the signal is out of range.
Supply Fluid Temp Set Point 1 Set point 1 of desi red fluid temperature at the outlet of the unit.
Supply Fluid Temp Set Point 2 Set point 2 of desi red fluid temperature at the outlet of the unit.
Supply Fluid Temperature Fluid temperature measured at the outlet of the unit.
Supply Fluid Under Temp Alarm
Threshold Threshold value used to generate a [Supply Fluid Under Temp] alarm.
Supply Fluid Under Temp Warning
Threshold Threshold value used to generate a [Supply Fluid Under Temp] warning.
Supply Fluid Under Temp [Supply Fluid Temperature] has dropped below a specified threshold.
Supply Heated Water Temp Set
Point Desired heated water temperature at the outlet of the unit.
Supply Refrigerant Temp Sensor
Issue
The supply refrigeramt temperature sensor is disconnected or the signal is out of
range.
System Control Mode System control mode.
System Date and Time The system date and time
System Event Acknowledge/Reset Reset and/or acknowledge all events.
System On/Off Control Turn system functionality on or off.
System Operating State Reason The reason the system is in the current operating state.
System Operating State Current operating state of the system.
System Status The operating status for the system
Unit Code Missing Uni t code has not been entered and saved.
Unit Off Unit was turned off.
Unit On Unit was turned on.
Unspecified General Event One or more unspecified events active. See local unit display for further details.
Table 17 Liebert HPC (Chiller) - Glossary (continued)
Controller Liebert iCOM® v4
Data Label Data Description