Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 60
System Status 30422 1
1 = Normal Operation
2 = Startup
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
System Control Mode 30423 1 0 = Internal (Auto)
1 = External (Manual)
Maintenance Ramp 30424 1 %
Auto Restart Delay 30425 40425 1 sec
System On/Off Control 30426 40426 1 0 = Off / 1 = On
System Event Acknowledge/Reset 40427 1 2 = Reset
4 = Acknowledge
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 20 Liebert XDP - Status and Coil
Controller Liebert iCOM® v4
Data Label Status Coil Number of Bits Notes
Pumps
Pump 1 Loss of Flow 10001 1 Active on Alarm
Pump 2 Loss of Flow 10002 1 Active on Alarm
Pump Short Cycle 10020 1 Active on Alarm
System Events
Fan Issue 10003 1 Active on Alarm
System Condensation Detected 10004 1 Active on Alarm
Customer Input 1 10005 1 Active on Alarm
Shutdown - Loss Of Power 10019 1 Active on Alarm
Water Under Floor 10021 1 Active on Alarm
Smoke Detected 10022 1 Active on Alarm
Service Required 10023 1 Active on Alarm
Unit Communication Lost 10262 1 Active on Alarm
RAM Battery Issue 10263 1 Active on Alarm
Master Unit Communication Lost 10264 1 Active on Alarm
Remote Shutdown 10265 1 Active on Alarm
Unit Code Missing 10266 1 Active on Alarm
Chilled Water
Supply Chilled Water Over Temp 10006 1 Active on Alarm
Supply Chilled Water Temp Sensor Issue 10007 1 Active on Alarm
Chilled Water Control Valve Position 10018 1 Active on Alarm
Refrigerant
Supply Refrigerant Over Temp 10008 1 Active on Alarm
Supply Refrigerant Under Temp 10009 1 Active on Alarm
Supply Refrigerant Temp Sensor Issue 10010 1 Active on Alarm
Table 19 Liebert XDC - Input and Holding (continued)
Controller Liebert iCOM® v4
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units