Modbus 485 and Modbus IP Protocols - UPS Systems
167 Liebert® IntelliSlot® Modbus/BACnet IP
System Input RMS Current Phase C The system input RMS current for Phase C
System Output Apparent Power The sum total apparent power of all system output phases
System Output Fault A fault has been detected in the system output
System Output Frequency The system output frequency
System Output Low Power Factor The system output power factor is low, resulting in reduced output
capacity
System Output Maximum Amp Rating System output maximum amperage rating
System Output Nominal Frequency The nominal (or rated) system output frequency
System Output Nominal Voltage The nominal (or rated) system output voltage
System Output Off The system output is off
System Output Pct Power Phase A The system output power on phase A as a percentage of the rated
capacity
System Output Pct Power Phase B The system output power on phase B as a percentage of the rated
capacity
System Output Pct Power Phase C The system output power on phase C as a percentage of the rated
capacity
System Output Pct Pwr (VA) Phs A The system output apparent power on phase A as a percentage of the
rated capacity
System Output Pct Pwr (VA) Phs B The system output apparent power on phase B as a percentage of the
rated capacity
System Output Pct Pwr (VA) Phs C The system output apparent power on phase C as a percentage of the
rated capacity
System Output Power Factor Phs A The system output power factor of phase A
System Output Power Factor Phs B The system output power factor of phase B
System Output Power Factor Phs C The system output power factor of phase C
System Output Power The sum total power of all system output phases
System Output RMS Current Phs A The system output RMS current for Phase A
System Output RMS Current Phs B The system output RMS current for Phase B
System Output RMS Current Phs C The system output RMS current for Phase C
System Output Voltage RMS A-B The system output RMS voltage between phases A and B
System Output Voltage RMS A-N The system output RMS voltage between phases A and Neutral
System Output Voltage RMS B-C The system output RMS voltage between phases B and C
System Output Voltage RMS B-N The system output RMS voltage between phases B and Neutral
System Output Voltage RMS C-A The system output RMS voltage between phases C and A
System Output Voltage RMS C-N The system output RMS voltage between phases C and Neutral
System Shutdown - EPO System shutdown due to Emergency Power Off (EPO)
System Shutdown - REPO System shutdown due to Remote Emergency Power Off (REPO)
System Status The operating status for the system
Total System Operating Time The cumulative operation time of the unit
Trap Filter Disconnect Trap filter disconnect
UPS Battery Status UPS battery status
UPS Module Type UPS module type
UPS Output on Bypass The output power is supplied by the bypass
UPS Output Source UPS output source
UPS System Output Source The UPS system's output power source
Table 57 Liebert NXL - 60Hz, UL version (Model 40) - Glossary (continued)
Data Label Data Description