BACnet Communications - UPS Systems
Liebert® IntelliSlot® Modbus/BACnet IP 354
ECO Mode
ECO Mode Operation State MultiState_Value 304 5454_1 RW 1 = disabled
2 = enabled
Continuous Operation - ECO Mode MultiState_Value 305 5455_1 RD 1 = disabled
2 = enabled
ECO Mode - EcoModeSchedule 1
Schedule Operation State - ECO Mode MultiState_Value 316 5461_1_1 RD 1 = disabled
2 = enabled
Schedule Action - ECO Mode MultiState_Value 317 5462_1_1 RD 1 = stop
2 = start
Schedule Day of Week - ECO Mode MultiState_Value 318 5463_1 _1 RD
1 = Unknown
2 = Monday
3 = Tuesday
4 = Wednesday
5 = Thursday
6 = Friday
7 = Saturday
8 = Sunday
ECO Mode - EcoModeSchedule 2
Schedule Operation State - ECO Mode MultiState_Value 329 5461_1_2 RD 1 = disabled
2 = enabled
Schedule Action - ECO Mode MultiState_Value 330 5462_1_2 RD 1 = stop
2 = start
Schedule Day of Week - ECO Mode MultiState_Value 331 5463_1 _2 RD
1 = Unknown
2 = Monday
3 = Tuesday
4 = Wednesday
5 = Thursday
6 = Friday
7 = Saturday
8 = Sunday
ECO Mode - EcoModeSchedule 14
Schedule Operation State - ECO Mode MultiState_Value 485 5461_1_14 RD 1 = disabled
2 = enabled
Schedule Action - ECO Mode MultiState_Value 486 5462_1_14 RD 1 = stop
2 = start
Schedule Day of Week - ECO Mode MultiState_Value 487 5463_1_14 RD
1 = Unknown
2 = Monday
3 = Tuesday
4 = Wednesday
5 = Thursday
6 = Friday
7 = Saturday
8 = Sunday
Tabl e 112 Lie ber t NXL - 50 Hz, CE version (Models 48 and 49)—Multistate Data
Data Label Object Type Instance Object Name Access Notes