BACnet Communications - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 282
XD System 1 Temperature Sensor 4
Remote Sensor Temperature Analog_Value 143 5059_1_4 RD
XD System 2
Cooling Capacity Analog_Value 154 5490_2 RD
Cooling Capacity Analog_Value 155 5491_2 RD
Hot Aisle Over Temp Threshold Analog_Value 156 5503_2 RW
Hot Aisle Under Temp Threshold Analog_Value 157 5504_2 RW
Cold Aisle Over Temp Threshold Analo g_Value 158 5506_2 RW
Cold Aisle Under Temp Threshold Analog_Value 159 5507_2 RW
XD System 2 Temperature Sensor 1
Remote Sensor Temperature Analog_Value 170 5059_2_1 RD
XD System 2 Temperature Sensor 2
Remote Sensor Temperature Analog_Value 181 5059_2_2 RD
XD System 2 Temperature Sensor 3
Remote Sensor Temperature Analog_Value 192 5059_2_3 RD
XD System 2 Temperature Sensor 4
Remote Sensor Temperature Analog_Value 203 5059_2_4 RD
XD System 20
Cooling Capacity Analog_Value 1234 5490_20 RD
Cooling Capacity Analog_Value 1235 5491_20 RD
Hot Aisle Over Temp Threshold Analog_Value 1236 5503_20 RW
Hot Aisle Under Temp Threshold Analog_Value 1237 5504_20 RW
Cold Aisle Over Temp Threshold Analo g_Value 1238 5506_20 RW
Cold Aisle Under Temp Threshold Analog_Value 1239 5507_20 RW
XD System 20 Temperature Sensor 1
Remote Sensor Temperature Analog_Value 1250 5059_20_1 RD
XD System 20 Temperature Sensor 2
Remote Sensor Temperature Analog_Value 1261 5059_20_2 RD
XD System 20 Temperature Sensor 3
Remote Sensor Temperature Analog_Value 1272 5059_20_3 RD
XD System 20 Temperature Sensor 4
Remote Sensor Temperature Analog_Value 1283 5059_20_4 RD
System Information
Auto Restart Delay Analog_Value 1294 4710_1 RW
Maintenance Ramp Analog_Value 1295 4870_1 RD
Calculated Next Maintenance Month Analog_Value 1296 4868_1 RD
Calculated Next Maintenance Year Analog_Value 1297 4869_1 RD
Time
System Date and Time Analog_Value 1308 4293_1 RW
Table 93 Liebert XDP, Liebert XDC - Analog Data (continued)
Controller Liebert iCOM® v4
Data Label Object Type Instance
Object
Name Access Notes