Modbus 485 and Modbus IP Protocols - Thermal Management Products
85 Liebert® IntelliSlot® Modbus/BACnet IPTable 28 Liebert DataMate, Liebert Mini-Mate Plus, Liebert Mini-Mate2 - Input andHolding - L0B
Controller Small Systems - L0B
Liebert Products
Liebert DataMate
Liebert Mini-Mate Plus
Liebert Mini-Mate2
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Temperature 40001 1 —
Humidity 40002 1 —
Cooling 40003 1 1=On / 0=Off
Heating 40004 1 1=On / 0=Off
Humidification 40005 1 1=On / 0=Off
Dehumidification 40006 1 1=On / 0=Off
Econ-o-Cycle 40007 1 1=On / 0=Off
Stages 40008 1 —
% Capacity 40009 1
Alarm Points
Communications 40289 1 Bit 0
Local Off 40289 1 Bi t 1
Remote Off 40289 1 Bit 2
High Temperature 40289 1 Bit 3
Low Temperature 40289 1 Bit 4
High Humidity 40289 1 Bit 5
Low Humidity 40289 1 Bit 6
Setpoints (View)
None 1 —
Control Points (Set)
Unit On/Off 4 0011 1 1=On / 0=Off (R/W)
Remote On/Off 40349 1 Bit 0 On=unit Off
Bit 1 On=unit On (W)
Trendable Points (Set)
Temperature 1 —
Humidity 1 —
Reports —— — —
Trend 1 —
Status 1 —
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.