Modbus 485 and Modbus IP Protocols - UPS Systems
199 Liebert® IntelliSlot® Modbus/BACnet IPTable 69 Liebert Series 610 SCC UPS - Status and Coil
Data Description Status Coil
Number
of Bits Scale Notes / Units
Auto Retransfer Primed 10049 1
Load On Inverter 10073 1
Load On Bypass 10074 1
Load On Bypass 10129 1
Manual Reset Transfer 10130 1
Emergency Transfer 10134 1
Output Switch open 10138 1
SBS Unable 10148 1
Output Frequency Off 1015 3 1
Output Overload 10154 1
System Emergency Off 10157 1
Input Power Supply Fail 10186 1
Input Phase Rotation Error 10191 1
Bypass Input Voltage Fail 10202 1
Output Under Voltage 10218 1
Output Over Voltage 10219 1
Module Alarm Active 10304 1
Customer Alarm 1 10313 1
Customer Alarm 2 10314 1
Customer Alarm 3 10315 1
Customer Alarm 4 10316 1
Customer Alarm 5 10317 1
Customer Alarm 6 10318 1
Customer Alarm 7 10319 1
Customer Alarm 8 10320 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.