Modbus 485 and Modbus IP Protocols - Thermal Management Products
49 Liebert® IntelliSlot® Modbus/BACnet IPTable 14 Liebert HPC (Chiller) - Status and Coil
Controller Liebert iCOM® v4
Data Label Status Coil
Number
of Bits Notes
Extra
Notes
Compressors
Compressor Not Stopping 10001 1 Active on Alarm 1, 2
Compressor Superheat Over Threshold 10002 1 Active on Alarm 2
Compressor 1
Compressor Hours Exceeded 10012 1 Active on Alarm 1, 2
Compressor High Head Pressure 10013 1 Active on Alarm 1, 2
Compressor Low Suction Pressure 10014 1 Active on Alarm 1, 2
Compressor Thermal Overload 10015 1 Active on Alarm 1, 2
Compressor Low Oil Pressure 10016 1 Active on Alarm 1, 2
Compressor Loss of Differential Pressure 10018 1 Active on Alarm 1, 2
Compressor Capacity Reduced 10019 1 Active on Alarm 1, 2
Compressor Capacity Normal 10020 1 Active on Alarm 2
Compressor Contactor Issue 10021 1 Active on Alarm 2
Compressor 2
Compressor Hours Exceeded 10029 1 Active on Alarm 1, 2
Compressor High Head Pressure 10030 1 Active on Alarm 1, 2
Compressor Low Suction Pressure 10031 1 Active on Alarm 1, 2
Compressor Thermal Overload 10032 1 Active on Alarm 1, 2
Compressor Low Suction Pressure 10033 1 Active on Alarm 1, 2
Compressor Loss of Differential Pressure 10035 1 Active on Alarm 1, 2
Compressor Capacity Reduced 10036 1 Active on Alarm 1, 2
Compressor Capacity Normal 10037 1 Active on Alarm 2
Compressor Contactor Issue 10038 1 Active on Alarm 2
Compressor 4
Compressor Hours Exceeded 10230 1 Active on Alarm 1, 2
Compressor High Head Pressure 10231 1 Active on Alarm 1, 2
Compressor Low Suction Pressure 10232 1 Active on Alarm 1, 2
Compressor Thermal Overload 10233 1 Active on Alarm 1, 2
Compressor Low Suction Pressure 10234 1 Active on Alarm 1, 2
Compressor Loss of Differential Pressure 10236 1 Active on Alarm 1, 2
Compressor Capacity Reduced 10237 1 Active on Alarm 1, 2
Compressor Capacity Normal 10238 1 Active on Alarm 2
Compressor Contactor Issue 10239 1 Active on Alarm 2
Condensers 1
Condenser Fan Issue 10046 1 Active on Alarm 1, 2
Low Condenser Refrigerant Pressure 10047 1 Active on Alarm 1, 2
Condenser Max Fan Speed Override 10048 1 Active on Alarm 1, 2
Condensers 2
Condenser Fan Issue 10058 1 Active on Alarm 1, 2
Low Condenser Refrigerant Pressure 10059 1 Active on Alarm 1, 2
Condenser Max Fan Speed Override 10060 1 Active on Alarm 1, 2
Condensers 4
Condenser Fan Issue 10066 1 Active on Alarm 1, 2
Low Condenser Refrigerant Pressure 10067 1 Active on Alarm 1, 2
Condenser Max Fan Speed Override 10068 1 Active on Alarm 1, 2