Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
103 Liebert® IntelliSlot® Modbus/BACnet IP
Panel Main Voltage Vy THD 30514 1 10 % THD
Panel Main Voltage Vz THD 30515 1 10 % THD
Panel Main Current Ix THD 30516 1 10 % THD
Panel Main Current Iy THD 30517 1 10 % THD
Panel Main Current Iz THD 30518 1 10 % THD
Panel Main Current Ix Crest Factor 30519 1 10
Panel Main Current Iy Crest Factor 30520 1 10
Panel Main Current Iz Crest Factor 30521 1 10
Panel 4
Columns of Breakers 30556 1
Number of Breakers 30557 1
Panel Main Voltage X-Y 30558 1 VAC
Panel Main Voltage Y-Z 30559 1 VAC
Panel Main Voltage Z-X 30560 1 VAC
Panel Main Voltage X-N 30561 1 VAC
Panel Main Voltage Y-N 30562 1 VAC
Panel Main Voltage Z-N 30563 1 VAC
Panel Main Current Ix 30564 1 A AC
Panel Main Current Iy 30565 1 A AC
Panel Main Current Iz 30566 1 A AC
Panel Main Neutral Current 30567 1 A AC
Panel Main Ground Current 30568 1 1 0 A AC
Panel Main Output Power (kVA) 30569 1 kVA
Panel Main Output Power (kW) 30570 1 kW
Panel Main Output kW-Hrs 30571 40571 2 10 kWH
Panel Main Output Power Factor 30573 1 100
Panel Main Output Percent Load 30574 1 - %
Panel Main Voltage Vx THD 30575 1 10 % THD
Panel Main Voltage Vy THD 30576 1 10 % THD
Panel Main Voltage Vz THD 30577 1 10 % THD
Panel Main Current Ix THD 30578 1 10 % THD
Panel Main Current Iy THD 30579 1 10 % THD
Panel Main Current Iz THD 30580 1 10 % THD
Panel Main Current Ix Crest Factor 30581 1 10
Panel Main Current Iy Crest Factor 30582 1 10
Panel Main Current Iz Crest Factor 30583 1 10
Table 36 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Input and Holding (continued)
Controller Liebert iCOM® v4
Liebert Products Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units