Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 16
Infrared Humidifier Flush Rate 30273 40273 1 % 1, 2, 3, 4, 5, 6
Fan Control Mode 30274 40274 1
0 = Auto
1 = Manual
2 = Economy
4 = Delta
1
Analog Input Reading 1 30275 1 100 1, 2, 3, 4, 5, 6
Analog Input Reading 2 30276 1 100 1, 2, 3, 4, 5, 6
Analog Input Reading 3 30277 1 100 1, 2, 3, 4, 5, 6
Analog Input Reading 4 30278 1 100 1, 2, 3, 4, 5, 6
System Control Mode 30280 1 0 = Internal (Auto)
1 = External (Manual) 1, 2, 3, 4, 5, 6
System Operating State Reason 30281 1
0 = Reason Unknown
1 = Network Display
2 = Alarm
3 = Schedule
4 = Remote System
5 = External Input
6 = Local Display
1, 2, 3, 4, 5, 6
Maintenance Ramp 30282 1 % 1, 2, 3, 4, 5, 6
Calculated Next Maintenance Month 30283 1 1, 2, 3, 4, 5, 6
Calculated Next Maintenance Year 30284 1 1, 2, 3, 4, 5, 6
Hot Water / Hot Gas Valve Open Position 30285 1 % 1, 2, 3, 4, 5, 6
Maintenance Tracking State 30286 1 0 = off
1 = on 1, 2, 3, 4, 5, 6
Customer Input 1 - Event Control 30287 40287 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Customer Input 1 - Event Type 30288 40288 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Customer Input 2 - Event Control 30289 40289 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Customer Input 2 - Event Type 30290 40290 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Customer Input 3 - Event Control 30291 40291 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Customer Input 3 - Event Type 30292 40292 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Customer Input 4 - Event Control 30293 40293 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Customer Input 4 - Event Type 30294 40294 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Ext Free Cooling Lockout - Event Control 30295 40295 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Ext Free Cooling Lockout - Event Type 30296 40296 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3,
Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes