Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
113 Liebert® IntelliSlot® Modbus/BACnet IP
Source 2 Overload 40290 1 Bit 3
Power Supply 2 Fault 40 290 1 Bit 4
Frequency Deviation 40290 1 Bit 5
Transfer Inhibit 40290 1 Bit 6
Auto Retransfer Primed 40290 1 Bit 7
Out of Synchronization 40290 1 Bit 8
Source 1 Failure 40290 1 Bit 9
Source 2 Failure 40290 1 Bit 10
Auto Retransfer Failed 40291 1 Bit 0
Overload 40291 1 Bit 1
Control Fuse 1 Blown 40291 1 Bit 2
Control Fuse 2 Blown �� 40291 1 Bit 3
Source 1 CB1 Open 40291 1 Bit 4
Source 2 CB2 Open 40291 1 Bit 5
Output CB3 Open 40291 1 Bit 6
Custom Alarm 1 40291 1 Bit 7
Custom Alarm 2 40291 1 Bit 8
Bypass CB4 Closed 40291 1 Bit 9
Bypass CB5 Closed 40291 1 Bit 10
Custom Alarm 3 40292 1 Bit 0
Custom Alarm 4 40292 1 Bit 1
Custom Alarm 5 40292 1 Bit 2
Custom Alarm 6 40292 1 Bit 3
Custom Alarm 7 40292 1 Bit 4
Custom Alarm 8 40292 1 Bit 5
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 38 Liebert STS, Liebert STS/PDU - Input and Holding - STS (continued)
Controller STS
Liebert Products Liebert STS
Liebert STS/PDU
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units