Modbus 485 and Modbus IP Protocols - UPS Systems

Liebert® IntelliSlot® Modbus/BACnet IP 118

3.3 UPS Systems

Table 40 Liebert APM™, Liebert NXC, Liebert NXR- Status and Coil

Data Label Status Coil
Number
of Bits Scale Notes / Units
System Status
Battery Auto Test In Progress 10001 1 Active on Alarm
Battery Equalize 10002 1 Active on Alarm
Battery Charging Inhibited 10003 1 Active on Alarm
On Generator 10004 1 Active on Alarm
System Events
System Input Power Problem 10015 1 Active on Alarm
Rectifier Failure 10016 ��� 1 Active on Alarm
Inverter Failure 10017 1 Active on Alarm
Bypass Not Available 10018 1 Active on Alarm
Battery Low 10019 1 Active on Alarm
LBS Inhibited 10020 1 Active on Alarm
System Fan Failure 10021 1 Active on Alarm
Equipment Over Temperature 10022 1 Active on Alarm
System Shutdown - EPO 10023 1 Active on Alarm
Bypass Static Switch Unavailable 10024 1 Active on Alarm
Bypass - Excess Auto Retransfers 10025 1 Active on Alarm
Parallel Comm Warning 10026 1 Active on Alarm
Power Supply Failure 10027 1 Active on Alarm
Battery Over Temperature 10028 1 Active on Alarm
System Input Phs Rotation Error 10029 1 Active on Alarm
Fuse Failure 10030 1 Active on Alarm
Inverter Overload Phase A 10031 1 Active on Alarm
Inverter Overload Phase B 10032 1 Active on Al arm
Inverter Overload Phase C 10033 1 Active on Alarm
MMS Overload 10034 1 Active on Alarm
Inverter Shutdown - Overload 10035 1 Active on Alarm
System Output Fault 10036 1 A ctive on Alarm
Internal Communications Failure 10037 1 Active on Alarm
Battery Charging Error 10038 1 Active on Alarm
System Input Current Imbalance 10039 1 Active on Alarm
Main Battery Disconnect Open 10040 1 Active on Alarm
Inverter Static Switch SCR Short 10041 1 Active on Alarm
Battery Not Qualified 10042 1 Active on Alarm
Battery Terminals Reversed 10043 1 Active on Alarm
Battery Converter Failure 10044 1 Active on Alarm
Inverter SCR Open 10045 1 Active on Alarm
Load Sharing Fault 10046 1 Active on Alarm
DC Bus Abnormal 10047 1 Active on Alarm
Mains Input Neutral Lost 10048 1 Active on Alarm
Load Impact Transfer 10049 1 Active on Alarm