BACnet Communications - Thermal Management Products
225 Liebert® IntelliSlot® Modbus/BACnet IP
System Events - iCOM DO Board 3
Digital Output Board Not Detected Binary_Value 349 5417_1_3 RD Active on Alarm 1, 2, 3,
4, 5, 6
Remote Sensors
Remote Sensor Average Over
Temperature Binary_Value 361 5593_1 RD Active on Alarm 2, 3, 4,
5, 6
Remote Sensor Average Under
Temperature Binary_Value 362 5594_1 RD Active on Alarm 2, 3, 4,
5, 6
Remote Sensor System Average Over
Temperature Binary_Value 363 5595_1 RD Active on Alarm 2, 3, 4,
5, 6
Remote Sensor System Average
Under Temperature Binary_Value 364 5596_1 RD Active on Alarm 2, 3, 4,
5, 6
Remote Sensors - Remote Sensor 1
Remote Sensor Over Temperature Binary_Value 376 5597_1_1 RD Active on Alarm 2, 3, 4,
5, 6
Remote Sensor Under Temperature Binary_Value 377 5598_1_1 RD Active on Alarm 2, 3, 4,
5, 6
Remote Sensor Issue Binary_Value 378 5060_1_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
Remote Sensors - Remote Sensor 2
Remote Sensor Over Temperature Binary_Value 390 5597_1_2 RD Active on Alarm 2, 3, 4,
5, 6
Remote Sensor Under Temperature Binary_Value 391 5598_1_2 RD Active on Alarm 2, 3, 4,
5, 6
Remote Sensor Issue Binary_Value 392 5060_1_2 RD Active on Alarm 2, 3, 4,
5, 6
Remote Sensors - Remote Sensor 10
Remote Sensor Over Temperature Binary_Value 502 5597_1_10 RD Active on Alarm 2, 3, 4,
5, 6
Remote Sensor Under Temperature Binary_Value 503 5598_1_10 RD Active on Alarm 2, 3, 4,
5, 6
Remote Sensor Issue Binary_Value 504 5060_1_10 RD Active on Alarm 2, 3, 4,
5, 6
Remote Sensor Over Temperature Binary_Value 502 5597_1_10 RD Active on Alarm 2, 3, 4,
5, 6
Remote Sensor Under Temperature Binary_Value 503 5598_1_10 RD Active on Alarm 2, 3, 4,
5, 6
Remote Sensor Issue Binary_Value 504 5060_1_10 RD Active on Alarm 2, 3, 4,
5, 6
Air Economizer
Air Economizer Emergency Override Binary_Value 516 5600_1 RD Active on Alarm 2, 3, 4,
5, 6
Air Economizer Reduced Airflow Binary_Value 517 5601_1 RD Active on Alarm 2, 3, 4,
5, 6
Electronic Expansion Valves
EEV Unspecified General Event Binary_Value 540 5625_1 RD Active on Alarm 4 , 5
Static Pressure
Static Pressure Sensor Issue Binary_Value 563 5629_1 RD Active on Alarm 3, 5, 6
High Static Pressure Binary_Value 564 5630_1 RD Active on Alarm 3, 5, 6
Table 76 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3,
Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Binary Data (continued)
Controller Liebert iCOM® v4
Data Description Object Type Instance
Object
Name Access Notes
Extra