BACnet Communications - Thermal Management Products
261 Liebert® IntelliSlot® Modbus/BACnet IP
Condenser Low Noise Mode - Interval Days Analog_Value 287 5550_1_1 RW
1 = Monday
2 = Tuesday
4 = Wednesday
8 = Thursday
16 = Friday
32 = Saturday
64 = Sunday
Condenser Low Noise Mode - Full Days Analog_Value 288 5551_1_1 RW
1 = Monday
2 = Tuesday
4 = Wednesday
8 = Thursday
16 = Friday
32 = Saturday
64 = Sunday
Condenser Low Noise Mode Start Time Analog_Value 289 5552_1_1 RW Units: Seconds
since Midnight
Condenser Low Noise Mode Stop Time Analog_Value 290 5553_1_1 RW Units: Seconds
since Midnight
Table 84 Liebert CRV - Analog Data (continued)
Controller Liebert iCOM® v4
Data Label Object Type Instance
Object
Name Access Notes