Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert® IntelliSlot® Modbus/BACnet IP 102
Panel Main Current Ix 30471 1 A AC
Panel Main Current Iy 30472 1 A AC
Panel Main Current Iz 30473 1 A AC
Panel Main Neutral Current 30474 1 A AC
Panel Main Ground Current 30475 1 1 0 A AC
Panel Main Output Power (kVA) 30476 1 kVA
Panel Main Output Power (kW) 30477 1 kW
Panel Main Output kW-Hrs 30478 40478 2 10 kWH
Panel Main Output Power Factor 30480 1 100
Panel Main Output Percent Load 30481 1 %
Panel Main Voltage Vx THD 30482 1 10 % THD
Panel Main Voltage Vy THD 30483 1 10 % THD
Panel Main Voltage Vz THD 30484 1 10 % THD
Panel Main Current Ix THD 30485 1 10 % THD
Panel Main Current Iy THD 30486 1 10 % THD
Panel Main Current Iz THD 30487 1 10 % THD
Panel Main Current Ix Crest Factor 30488 1 10
Panel Main Current Iy Crest Factor 30489 1 10
Panel Main Current Iz Crest Factor 30490 1 10
Panel 2
Columns of Breakers 30494 1
Number of Breakers 30495 1
Panel Main Voltage X-Y 30496 1 VAC
Panel Main Voltage Y-Z 30497 1 VAC
Panel Main Voltage Z-X 30498 1 VAC
Panel Main Voltage X-N 30499 1 VAC
Panel Main Voltage Y-N 30500 1 VAC
Panel Main Voltage Z-N 30501 1 VAC
Panel Main Current Ix 30502 1 A AC
Panel Main Current Iy 30503 1 A AC
Panel Main Current Iz 30504 1 A AC
Panel Main Neutral Current 30505 1 A AC
Panel Main Ground Current 30506 1 1 0 A AC
Panel Main Output Power (kVA) 30507 1 kVA
Panel Main Output Power (kW) 30508 1 kW
Panel Main Output kW-Hrs 30509 40509 2 10 kWH
Panel Main Output Power Factor 30511 1 100
Panel Main Output Percent Load 30512 1 %
Panel Main Voltage Vx THD 30513 1 10 % THD
Table 36 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Input and Holding (continued)
Controller Liebert iCOM® v4
Liebert Products Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units