Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert® IntelliSlot® Modbus/BACnet IP 158
Sum of MMS Output RMS Currents
for Phase B 30512 1 Units : A AC 1+N, SCC
Sum of MMS Output RMS Currents
for Phase C 30513 1 Units : A AC 1+N, SCC
MMS Output Frequency 30514 1 10 Units : Hz 1+N, SCC
MMS Output Power 30515 1 Units : kW 1+N, SCC
MMS Output Apparent Power 30516 1 Units : kVA 1+N, SCC
MMS Output Power Factor
Phase A 30517 1 100 1+N, SCC
MMS Output Power Factor
Phase B 30518 1 100 1+N, SCC
MMS Output Power Factor
Phase C 30519 1 100 1+N, SCC
MMS Output Pct Power Phase A 30520 1 Units : % 1+N, SCC
MMS Output Pct Power Phase B 30521 1 Units : % 1+N, SCC
MMS Output Pct Power Phase C 30522 1 Units : % 1+N, SCC
MMS Output Pct Apparent Pwr
(kVA) Phase A 30523 1 Units : % 1+N, SCC
MMS Output Pct Apparent Pwr
(kVA) Phase B 30524 1 Units : % 1+N, SCC
MMS Output Pct Apparent Pwr
(kVA) Phase C 30525 1 Units : % 1+N, SCC
Number of Redundant Modules 30526 1 1+N, SCC
MMS Module Number 30527 1 1+N, SCC
Number of Modules in an MMS 30528 1 1+N, SCC
Module Output Breaker for
Module 1 (MOB1) 30529 — 1 —
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 2 (MOB2) 30530 — 1 —
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 3 (MOB3) 30531 — 1 —
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 4 (MOB4) 30532 — 1 —
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 5 (MOB5) 30533 — 1 —
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 6 (MOB6) 30534 — 1 —
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 7 (MOB7) 30535 — 1 —
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 8 (MOB8) 30536 — 1 —
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Table 56 Liebert NXL - 60Hz, UL version (Model 40) - Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Regs Scale Units / Notes
NXL