Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 28
Compressor Utilization Present compressor utilization expressed as a percentage of the maximum rated
capacity.
Condenser Circuit Unspecified
General Event
One or more unspecified condenser circuit events active. See local unit display for
further details.
Condenser Issue - Event Control
Enable/disable the activation of the [Condenser Issue] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any
active event list or in any event history list.
Condenser Issue - Event Type The event type for the [Condenser Issue] event.
Condenser Issue Condenser is not operating within its operational parameters.
Condenser Low Noise Mode - Full
Days Days of the week selected for low noise mode full day scheduling.
Condenser Low Noise Mode -
Interval Days Days of the week selected for low noise mode interval scheduling.
Condenser Low Noise Mode Max
Fan Speed Maximum fan speed when condenser is placed in low noise mode.
Condenser Low Noise Mode
Schedule Control Enable/disable scheduled control of condenser low noise mode.
Condenser Low Noise Mode Start
Time The time of day at which the condenser will transition into low noise mode.
Condenser Low Noise Mode State State of condenser low noise mode scheduler control.
Condenser Low Noise Mode Stop
Time The time of day at which the condenser will transition out of low noise mode.
Condenser Normal Mode Max Fan
Speed Maximum fan speed when condenser is not in low noise mode.
Condenser TVSS Issue The condenser Transient Voltage Surge Suppressor or Surge Protection Device has
failed.
Condenser Unit Unspecified
General Event
One or more unspecified condenser unit events active. See local unit display for
further details.
Condenser VFD Issue The condenser fan Variable Frequency Drive is offline.
Cooling Capacity Cooling capacity in use, expressed as a percentage of the maximum rated capacity.
Cooling Control Temperature Temperature value being used for cooling capacity control. This value is compared
against the temperature set point to determine the amount of cooling to be applied.
Cooling State Cooling operational state.
Customer Input 1 - Event Control
Enable/disable the activation of the [Customer Input 1] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any
active event list or in any event history list.
Customer Input 1 - Event Type The event type for the [Customer Input 1] event.
Customer Input 1 Customer Input 1
Customer Input 2 - Event Control
Enable/disable the activation of the [Customer Input 2] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any
active event list or in any event history list.
Customer Input 2 - Event Type The event type for the [Customer Input 2] event.
Customer Input 2 Customer Input 2
Customer Input 3 - Event Control
Enable/disable the activation of the [Customer Input 3] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any
active event list or in any event history list.
Customer Input 3 - Event Type The event type for the [Customer Input 3] event.
Customer Input 3 Customer Input 3
Table 10 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3,
Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Glossary (continued)
Controller Liebert iCOM® v4
Data Label Data Description