BACnet Communications - UPS Systems
347 Liebert® IntelliSlot® Modbus/BACnet IP
MultiModule
Multi-module System Output Voltage RMS A-B Analog_ Value 155 4801_1 RD Units: VAC
Multi-module System Output Voltage RMS B-C Analog_Value 156 4802_1 RD Units: VAC
Multi-module System Output Voltage RMS C-A Analog_Value 157 4803_1 RD Units: VAC
Multi-module System Output Voltage RMS A-N Analog_Value 158 4804_1 RD Units: VAC
Multi-module System Output Voltage RMS B-N Analog_Value 159 4805_1 RD Units: VAC
Multi-module System Output Voltage RMS C-N Analog_Value 160 4806_1 RD Units: VAC
Sum of MMS Output RMS Currents for Phase A Analog_Value 161 4807_1 RD Units: A AC
Sum of MMS Output RMS Currents for Phase B Analog_Value 162 4808_1 RD Units: A AC
Sum of MMS Output RMS Currents for Phase C Analog_Value 163 4809_1 RD Units: A AC
MMS Output Frequency Analog_Value 164 4810_1 RD Units: Hz
MMS Output Power Analog_Value 165 4811_1 RD Units: kW
MMS Output Apparent Power Analog_Value 166 4812_1 RD Units: kVA
MMS Output Power Factor Phase A Analog_Value 167 4813_1 RD
MMS Output Power Factor Phase B Analog_Value 168 4814_1 RD
MMS Output Power Factor Phase C Analog_Value 169 4815_1 RD
MMS Output Pct Power Phase A Analog_Value 170 4816_1 RD Units: %
MMS Output Pct Power Phase B Analog_Value 171 4817_1 RD Units: %
MMS Output Pct Power Phase C Analog_Value 172 4818_1 RD Units: %
MMS Output Pct Apparent Pwr (kVA) Phase A Analog_Value 173 4819_1 RD Units: %
MMS Output Pct Apparent Pwr (kVA) Phase B Analog_Value 174 4820_1 RD Units: %
MMS Output Pct Apparent Pwr (kVA) Phase C Analog_Value 175 4821_1 RD Units: %
Number of Redundant Modules Analog_Value 176 4822_1 RD
MMS Module Number Analog_Value 177 4829_1 RD
Number of Modules in a MMS Analog_Value 178 4833_1 RD
Intelligent Paralleling
Intelligent Parallel Minimum Redundancy Analog_Value 189 5451_1 RD
Intelligent Parallel Maximum Time in Standby Analog_Value 190 5452_1 RD Units: day
ECO Mode
Maximum Auto Suspensions - ECO Mode Analog_Value 201 5459_1 RD
Restart Delay - ECO Mode Analog_Value 202 5460_1 RD Units: min
Time Remaining - ECO Mode Analog_Value 203 5466_1 RD Units: min
ECO Mode - EcoModeSchedule 1
Schedule Hour - ECO Mode Analog_Value 214 5464_1_1 RD Uni ts: hr
Schedule Minute - ECO Mode Analog_Value 215 5465_1_1 RD Units: min
ECO Mode - EcoModeSchedule 2
Schedule Hour - ECO Mode Analog_Value 226 5464_1_2 RD Uni ts: hr
Schedule Minute - ECO Mode Analog_Value 227 5465_1_2 RD Units: min
ECO Mode - EcoModeSchedule 14
Schedule Hour - ECO Mode Analog_Value 370 5464_1_14 RD Units: hr
Schedule Minute - ECO Mode Analog_Value 371 5465_1_14 RD Units: min
Tabl e 111 Lie ber t NXL - 50 Hz, CE version (Models 48 and 49)—Analog Data
Data Label Object Type Instance Object Name Access Notes