BACnet Communications - UPS Systems
343 Liebert® IntelliSlot® Modbus/BACnet IP
Rectifier
Rectifier Failure Binary_Value 160 4295_1 RD Active on Alarm
Vdc Backfeed Binary_Value 162 5879_1 RD Active on Alarm
Rectifier Configuration Change Request Binary_Value 163 5880_1 RD Active on Alarm
System
System Fan Failure - Redundant Binary_Value 174 4749_1 RD Active on Alarm
Multiple Fan Failure Binary_Value 175 4750_1 RD Active on Alarm
Internal Communications Failure Binary_Value 176 4300_1 RD Active on Alarm
UPS Output on Bypass Binary_ Value 177 4298_1 RD Active on Alarm
Output Load on Maint. Bypass Binary_Value 178 4299_1 RD Active on Alarm
Backfeed Breaker Open Bina ry_Value 179 4325_1 RD Active on Alarm
Auto Restart In Progress Binary_Value 180 4316_1 RD Active on Alarm
Power Supply Failure Binary_Value 181 4314_1 RD Active on Alarm
Auto Restart Inhibited - Ext Binary_Value 183 4317_1 RD Active on Alarm
Automatic Restart Failed Binary_Value 184 4439_1 RD Active on Alarm
Main Controller Fault Binary_Value 185 4753_1 RD Active on Alarm
Fuse Failure Binary_Value 186 4440_1 RD Active on Alarm
System Controller Error Binary_Value 187 4441_1 RD Active on Alarm
System Breaker(s) Open Failure Bina ry_Value 188 4442_1 RD Active on Alarm
System Breaker(s) Close Failure Binary_Value 189 4754_1 RD Active on Alarm
Input Filter Cycle Lock Binary_Value 190 4755_1 RD Active on Alarm
EMO Shutdown Binary_Value 191 5769_1 RD Active on Alarm
Service Code Active Binary_Value 192 4756_1 RD Active on Alarm
LBS Active Binary_Value 193 4757_1 RD Active on Alarm
LBS Inhibited Binary_Value 194 475 8_1 RD Active on Alarm
Regeneration Active Binary_Value 195 5881_1 RD Active on Alarm
Regeneration Operation Terminated Binary_Value 196 5882_1 RD Active on Alarm
Regeneration Operation Failure Binary_Value 197 5883_1 RD Active on Alarm
Leading Power Factor Binary_Value 198 4759_1 RD Active on Alarm
Controls Reset Required Binary_Value 199 4760_1 RD Active on Alarm
MultiModule
Loss of Redundancy Binary_Value 212 4825_1 RD Active on Alarm
MMS Overload Binary_Value 215 4831_1 RD Active on Alarm
MMS On Battery Binary_Value 216 4834_1 RD Active on Alarm
MMS Module Alarm Active Binary_Value 218 5145_1 RD Active on Alarm
Program Input Signals
Program Input Contact 01 Binary_Value 229 5884_1 RD Active on Alarm
Program Input Contact 02 Binary_Value 230 5885_1 RD Active on Alarm
Program Input Contact 03 Binary_Value 231 5886_1 RD Active on Alarm
Program Input Contact 04 Binary_Value 232 5887_1 RD Active on Alarm
Program Input Contact 05 Binary_Value 233 5888_1 RD Active on Alarm
Program Input Contact 06 Binary_Value 234 5889_1 RD Active on Alarm
Program Input Contact 07 Binary_Value 235 5890_1 RD Active on Alarm
Program Input Contact 08 Binary_Value 236 5891_1 RD Active on Alarm
Tabl e 110 Lie ber t NXL - 50 Hz, CE version (Models 48 and 49)—Binary Data
Data Label
Object
Type Instance
Object
Name Access Notes