BACnet Communications - UPS Systems
335 Liebert® IntelliSlot® Modbus/BACnet IP
Continuous Operation - ECO Mode This setting gives the user the ability to Enable/Disable ECO Mode
continuous operation.
Controls Reset Required A controls reset is required due to one or more critical settings changing
DC Bus Current
The current at the battery input terminals. In charging mode, the current will
be a positive value. In discharging mode, the current will be a negative
value
DC Bus Ground Fault - Negative A ground fault has been detected on the negative DC Bus link
DC Bus Ground Fault - Positive A ground fault has been detected on the positive DC Bus link
DC Bus Qualification Status dc bus qualification status
DC Bus Voltage The voltage between the positive and negative terminals of the DC bus at
the battery input
ECO Mode Active Conditions for Activation or Automatic Reactivation have been satisfied.
ECO Mode Operation State This setting is used to enable or disable ECO Mode.
ECO Mode Suspended ECO Mode session is suspended.
EMO Shutdown An Emergency Module Off command has been detected.
Equipment Over Temperature Equipment over temperature summary event
Equipment Temperature Sensor Fail One or more temperature sensors report a temperature outside of the range
of expected operation.
Excess ECO Suspends Number of automatic suspensions has exceeded the ECO Mode -
Maximum Auto Suspensions setting.
Fuse Failure A summary event indicating one or more fuse failures
Inlet Air Over Temperature The inlet air exceeds the maximum temperature threshold
Inlet Air Temperature The temperature of the inlet air
Input Breaker (CB1/RIB) Input breaker (CB1/RIB)
Input Contact 01 The external input contact 1
Input Contact 02 The external input contact 2
Input Contact 03 The external input contact 3
Input Contact 04 The external input contact 4
Input Contact 05 The external input contact 5
Input Contact 06 The external input contact 6
Input Contact 07 The external input contact 7
Input Contact 08 The external input contact 8
Input Contact 09 The external input contact 9
Input Contact 10 The external input contact 10
Input Contact 11 The external input contact 11
Input Contact 12 The external input contact 12
Input Contact 13 The external input contact 13
Input Contact 14 The external input contact 14
Input Contact 15 The external input contact 15
Input Contact 16 The external input contact 16
Input Filter Cycle Lock The input filter disconnect is open due to exceeding the maximum number
of cycles.
Input Isolation Transformer Input isolation transformer
Input Qualification Status input qualification status
Intelligent Parallel Maximum Time in Standby The maximum time a module can be in standby mode due to Intelligent
Paralleling.
Table 109 Liebert NXL - 60Hz, UL version (Model 40) - Glossary (continued)
Data Label Data Description