BACnet Communications - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 284
Refrigerant
Supply Refrig Over Temp - Event Control Multistate_Value 41 4635_1 RD 1 = Disabled
2 = Enabled
Supply Refrig Over Temp - Event Type Mul tistate_Value 42 4636_1 RW
1 = Message
2 = Warning
3 = Alarm
Supply Refrig Under Temp - Event Control Multistate_Value 43 4638_1 RD 1 = Disabled
2 = Enabled
Supply Refrig Under Temp - Event Type Multistate_Value 44 4639_1 RW
1 = Message
2 = Warning
3 = Alarm
Supply Refrig Temp Sensor Issue - Event Control Multistate_Value 45 4641_1 RD 1 = Disabled
2 = Enabled
Supply Refrig Temp Sensor Issue - Event Type Multistate_Value 46 4642_1 RW
1 = Message
2 = Warning
3 = Alarm
Fluid
Supply Fluid Over Temp - Event Control M ultistate_Value 57 4646_1 RD 1 = Disabled
2 = Enabled
Supply Fluid Over Temp - Event Type Multistate_Value 58 4647_1 RW
1 = Message
2 = Warning
3 = Alarm
Supply Fluid Under Temp - Event Control Multistate_Value 59 4649_1 RD 1 = Disabled
2 = Enabled
Supply Fluid Under Temp - Event Type Multistate_Value 60 4650_1 RW
1 = Message
2 = Warning
3 = Alarm
Supply Fluid Temp Sensor Issue - Event Control Multistate_Value 61 465 2_1 RD 1 = Disabled
2 = Enabled
Supply Fluid Temp Sensor Issue - Event Type Multistate_Value 62 4653_1 RW
1 = Message
2 = Warning
3 = Alarm
Pumps
Pump 1 State Multistate_Value 73 4654_1 RD 1 = Off / 2 = On
Pump 2 State Multistate_Value 74 4655_1 RD 1 = Off / 2 = On
Pump 1 Loss of Flow - Event Control Multistate_Value 75 4657_1 RW 1 = Disabled
2 = Enabled
Pump 1 Loss of Flow - Event Type Multistate_Value 76 4658_1 RW
1 = Message
2 = Warning
3 = Alarm
Pump 2 Loss of Flow - Event Control Multistate_Value 77 4660_1 RW 1 = Disabled
2 = Enabled
Pump 2 Loss of Flow - Event Type Multistate_Value 78 4661_1 RW
1 = Message
2 = Warning
3 = Alarm
Pump Short Cycle - Event Control Multistate_Value 79 4663_1 RD 1 = Disa bled
2 = Enabled
Pump Short Cycle - Event Type Multistate_Value 80 4664_1 RW
1 = Message
2 = Warning
3 = Alarm
Table 94 Liebert XDP, Liebert XDC - Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label Object Type Instance
Object
Name Access Notes