BACnet Communications - Thermal Management Products
231 Liebert® IntelliSlot® Modbus/BACnet IP
Humidifier
Humidifier Hours Analog_Value 186 5369_1 RW Units: hr 1, 2, 3,
4, 5, 6
Humidifier Hours Threshold Analog_Value 187 5370_1 RW Units: hr 1, 2, 3,
4, 5, 6
Infrared Humidifier Flush Rate Analog_Value 188 5445_1 RW Units: % 1, 2, 3,
4, 5, 6
Dehumidifier
Dehumidifier Hours Ana log_Value 199 5371_1 RW Units: hr 1, 2, 3,
4, 5, 6
Dehumidifier Hours Threshold Analog_Value 200 5372_1 RW Units: hr 1, 2, 3,
4, 5, 6
Fan
Fan Speed Maximum Set Point Ana log_Value 211 5050_1 RW Units: % 1, 2, 3,
4, 5, 6
Fan Hours Analog_Value 212 5374_1 RW Units: hr 1, 2, 3,
4, 5, 6
Fan Hours Threshold Analog_Value 213 5375_1 RW Units: hr 1, 2, 3,
4, 5, 6
Fan Speed Minimum Set Point Analog_Value 214 5051_1 RW Units: % 2, 3, 4,
5, 6
Fan Speed Temperature Set
Point Analog_Value 215 5585_1 RW Units: deg C 2, 3, 4,
5, 6
Fan Speed Temperature Set
Point Analog_Value 10215 5585_1_deg_F RW Units: deg F 2, 3, 4,
5, 6
Analog Inputs 1
Analog Input Reading Analog_ Value 224 5378_1 RD 1, 2, 3,
4, 5, 6
Analog Inputs 2
Analog Input Reading Analog_ Value 235 5378_2 RD 1, 2, 3,
4, 5, 6
Analog Inputs 4
Analog Input Reading Analog_ Value 257 5378_4 RD 1, 2, 3,
4, 5, 6
System Info
BMS Timeout Period Analog_Value 268 5075_1 RW Units: min 1, 2, 3,
4, 5, 6
Auto Restart Delay Analog_Value 269 4710_1 RW Units: sec 1, 2, 3,
4, 5, 6
Standby Units Analog_Value 270 5314_1 RW 2, 3, 4,
5, 6
System Operations
Fan Speed Analog_Value 280 5077_1 RD Units: % 1, 2, 3,
4, 5, 6
Compressor Utilization Analog_Value 281 5078_1 RD Units: % 1
Free Cooling Valve Open
Position Analog_Value 282 5379_1 RD Units: % 1, 2, 3,
4, 5, 6
Maintenance Ramp Analog_Value 283 4870_1 RD Units: % 1, 2, 3,
4, 5, 6
Table 78 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3,
Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Analog Data (continued)
Data Label Object Type
Instanc
eObject Name
Acces
sNotes
Extra
Notes