Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert® IntelliSlot® Modbus/BACnet IP 150
Controls Reset Required 10397 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS
Battery Test Failed 10398 1 Active on Alarm N+1, 1+N, 1+1, SMS
Auto Restart Inhibited - Ext 10399 1 Active on Alarm SCC, SMS
Battery Test Inhibited 10400 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Equalize 10401 1 Active on Alarm N+1, 1+N, 1+1, SMS
Backfeed Breaker Open 10402 1 Active on Alarm SCC, 1+N, 1+1, SMS
On Generator 10403 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS
Power Supply Failure 10404 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS
Battery Ground Fault 10405 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Charging Error 10406 1 Active on Alarm N+1, 1+N, 1+1, SMS
System Input Power Problem 10407 1 Active on Alarm N+1, 1+N, 1+1, SMS
System Input Current Limit 1 0408 1 Active on Alarm N+1, 1+N, 1+1, SMS
Internal Communications Failure 10409 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS
System Controller Error 10410 1 Active on Al arm SCC, N+1, 1+N, 1+1, SMS
Output
Output Of/Uf 10510 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS
MultiModule
Parallel Comm Warning 10521 1 Active on Alarm SCC, N+1, 1+N, 1+1
System Comm Fail 10522 1 Active on Alarm SCC, N+1, 1+N, 1+1
Loss of Redundancy 10523 1 Active on Alarm SCC, 1+N, 1+1
BPSS Startup Inhibit 10524 1 Active on Alarm Deprecated
MMS Transfer Inhibit 10525 1 Active on Alarm SCC, 1+N, 1+1
MMS Retransfer Inhibit 10526 1 Active on Alarm SCC, 1+N, 1+1
MMS Loss of Sync Pulse 10527 1 Active on Alarm Deprecated
MMS Overload 10528 1 Active on Alarm SCC
MMS On Battery 10529 1 Active on Alarm SCC, 1+N, 1+1
MMS Low Battery Warning 10530 1 Active on Alarm SCC, 1+N, 1+1
MMS Module Alarm Active 10531 1 Active on Alarm SCC
MMS Sharing Calib Active 10532 1 Active on Alarm SCC
Intelligent Paralleling
Module In Standby - Intelligent Paralleling 10543 1 Active on Alarm SCC, N+1, 1+N, 1+1
ECO Mode
ECO Mode Active 10554 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS
ECO Mode Suspended 10555 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS
Excess ECO Suspends 10556 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS
System
LBS Active - Master 10567 1 Active on Alarm SCC, 1+N, 1+1, SMS
LBS Active - Slave 10568 1 Active on Alarm SCC, 1+N, 1+1, SMS
EMO Shutdown 10575 1 Active on Alarm SMS, 1+N, N+1, SCC
Cont Tie Active 10576 1 Active on Alarm SMS, 1+N, N+1, SCC
User kWh Reset 10577 1 Active on Alarm SMS, 1+N, N+1, SCC
Peak kW Reset 10578 1 Active on Alarm SMS, 1+N, N+1, SCC
Environment
Outlet Air Overtemperature Limit 10580 1 Active on Alarm SCC, SMS, 1+N, N+1
Service Reminder
Service Required 10590 1 Active on Alarm SMS, 1+N, N+1, SCC
Table 55 Liebert NXL - 60Hz, UL version (Model 40) - Status and Coil (continued)
Data Label Status Coil # of Bits Notes NXL Type