BACnet Communications - UPS Systems
319 Liebert® IntelliSlot® Modbus/BACnet IP
Input Contact 09 Binary_Value 146 4278_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Input Contact 10 Binary_Value 147 4279_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Input Contact 11 Binary_Value 148 4280_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Input Contact 12 Binary_Value 149 4281_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Input Contact 13 Binary_Value 150 4282_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Input Contact 14 Binary_Value 151 4283_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Input Contact 15 Binary_Value 152 4284_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Input Contact 16 Binary_Value 153 4285_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Rectifier
Rectifier Failure Binary_Value 164 4295_1 RD Active on Alarm SMS, 1+N,
N+1
Rectifier Operation Inhibit-Ext Binary_Value 165 4296_1 RD Active on Alarm CE models
only
System
System Fan Failure - Redundant Binary_Value 176 4749_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Multiple Fan Failure Binary_Value 177 4750_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Internal Communications Failure Binary_Value 178 4300_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
UPS Output on Bypass Binary_Value 179 4298_1 RD Active on Alarm SMS, 1+N,
SCC
Output Load on Maint. Bypass Binary_Value 180 4299_1 RD Active on Alarm SMS, 1+N,
SCC
Backfeed Breaker Open Binary_Value 181 4325_1 RD Active on Alarm SMS, 1+N,
SCC
Auto Restart In Progress Binary_Value 182 4316_1 RD Active on Alarm SMS
Power Supply Failure Binary_Value 183 4314_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
On Generator Binary_Value 184 4315_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Auto Restart Inhibited - Ext Binary_Value 185 4317_1 RD Active on Alarm S MS
Automatic Restart Failed Binary_Value 186 4439_1 RD Active on Alarm SMS
Main Controller Fault Binary_Value 187 4753_1 RD Active on Alarm SMS, 1+N,
N+1
Fuse Failure Binary_Value 188 4440_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
System Controller Error Binary_Value 189 4441_1 RD Active on Alarm SMS, 1+N,
N+1
System Breaker(s) Open Failure Binary_Value 190 4442_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
System Breaker(s) Close Failure Binary_Value 191 4754_1 RD Active on Alarm SMS, 1+N,
N+1, SCC
Table 106 Liebert NXL- 60Hz, UL version (Model 40) - Binary Data (continued)
Data Label
Object
Type Instance
Object
Name Access Notes
Liebert
NXL Type